62
LDM Series Instruction Manual —
P/N 15885:H3 8/12/2019
AFP-200 (UL 8th)
Configuration for the LDM-32 and AFP-200
Figure E.2 illustrates configuration of the LDM to annunciate the Active state for up to 56 zones (no zone troubles) with the last eight
points (P57 through P64) dedicated to the AFP-200 system function LEDs listed below.
Figure E.3 illustrates wiring the LDM to annunciate the active and trouble states for all 99 zones with the first eight points (J5: P1
through P8 and J6: P1 through P8) dedicated to AFP-200 functions listed below.
J6
J5
OUTPUTS
J7
J8
J8
wire to
LEDs
25 - 32
System Functions *
1 - 8
33 - 40
9 - 16
41 - 48
17 - 24
49 - 56
Address #1
LDM-32
LDM-E32
* System Status Indicators
System Alarm
not used
View of LDM-32
*It is assumed that the '8-Point
Shift' will be selected only on
systems containing less than 56
software zones or a total of 64
annunciator points or less.
Figure E.2 Active Status of Software Zones with 8-Point Shift
J6
J5
OUTPUTS
J7
J8
Alarm
Alarm
Alarm
Alarm
Trouble
Trouble
Trouble
Trouble
J6
J5
OUTPUTS
Address #1
LDM-32
1st LDM-E32
2nd LDM-E32
3rd LDM-E32
System Status Indicators*
13 - 16
29 - 32
45 - 48
1 - 4
17 - 20
33 - 36
49 - 52
9 - 12
25 - 28
41 - 44
5 - 8
21 - 24
37 - 40
53 - 56
Address #2
LDM-32
1st LDM-E32
2nd LDM-E32
57 - 60
73 - 76
89 - 92
61 - 64
77 - 80
93 - 99
65 - 68
81 - 84
69 - 72
85 - 88
* System Status Indicators
View of LDM-32
not used
not used
not used
not used
Supervisory (Yellow LED)
Pre-Alarm
AC Fail (Yellow LED)
Panel Trouble
not used
not used
Signals Silenced (Yellow LED)
System Trouble (Yellow LED)
System Alarm (Red
LED)
not
It is assumed that this module/expander
annunciates points 64-99.
Zones 90-99 are special function zones:
•
Z90 Presignal Time Run
•
Z91 Time Started/Release
•
Z92 Time Started/Release
•
Z93 Time Started/Release
•
Z94 Time Started/Release
•
Z95 Time Ctl Active
•
Z96Time Ctl Active
•
Z97 Holiday Active
•
Z98 Tornado
•
Z99 Pre-alarm
Figure E.3 Activation and Trouble Status Annunciation