LDM Series Instruction Manual —
P/N 15885:H3 8/12/2019
37
AIM-200 Point Annunciation
System 5000 (UL 8th)
Figure B.4 illustrates the configuration of LDMs to annunciate alarms for up to 120 zones (no zone troubles) with the first eight points
(P1 through P8) dedicated to the System 5000unctions listed below. (Control switches do not function in Alarm Only configuration).
Figure B.5 illustrates the configuration of LDMs to annunciate alarms for up to 56 zones (no zone troubles) with the last eight points
(P57 through P64) dedicated to the System 5000 function annunciations listed below. (Control Switches do not function in Alarm Only
mode).
J6
J5
OUTPUTS
J7
J8
J5
Address #1
LDM-32
LDM-E32
Address #2
LDM-32
LDM-E32
System Functions *
25 - 32
1 - 8
33 - 40
9 - 16
41 - 48
73 - 80
105 - 112
17 - 24
49 - 56
81 - 88
113 - 120
65 - 72
97 - 104
57 - 64
89 - 96
wire to
LEDs
view of LDM-32
* System Status Indicators
not
Notification Circuit #1 ON (Green LED)
System Alarm (Red LED)
Notification Circuit #2 ON (Green LED)
Municipal Tie ON (Red LED)
Alarm Relay ON (Red LED)
*It is assuming this module/expander annunciates points (circuits) 65-128 and is not
functioning as a Receive Only annunciator.
Figure B.4 Alarm Only Operation Without 8-Point Shift
J6
J5
OUTPUTS
J7
J8
J8
Address #1
LDM-32
LDM-E32
25 - 32
System Functions *
1 - 8
33 - 40
9 - 16
41 - 48
17 - 24
49 - 56
wire to
LEDs
* System Status Indicators
not
used
Notification Circuit #1 ON (Green LED)
System Alarm (Red LED)
Notification Circuit #2 ON (Green LED)
Municipal Tie ON (Red LED)
Alarm Relay ON (Red LED)
view of LDM-32
*It is assumed that the '8-Point Shift' will be selected only on systems containing less than 56
zones/points or a total of 64 annunciator points or less.
Figure B.5 Alarm Only Operation with 8-Point Shift