74
Notifier FirstCommand Series Manual —
P/N LS10001-001NF-E:H 1/8/2018
Operating Instructions
Operation
• Turn the “System in Use” LED on steady
• Activate the “MNS active” relay (if the system is programmed for mass notification)
• Activate the NAC output (if programmed to do so for mass notification)
• Play and repeat a leading tone (if programmed)
• Play and repeat the appropriate audio message (if programmed to repeat)
• Play an inter-message tone (if programmed)
• Play a primary alert tone only (if programmed)
• Store the event in the history log
4.4.8 Alarm/Alert Restoral, System Configured for Mass Notification Only
Upon restoral the system will:
• Turn the speaker zone LEDs off
• Turn the speaker circuits off
• Turn the audio amplifier(s) off
• Turn the 24 VDC aux. power output off (if programmed)
• Turn the speaker volume control override off
• De-activate the “MNS active” output relay
• De-activate the NAC output (if programmed to do so for mass notification)
• Turn the “System in Use” LED off
4.4.9 Alarm/Alert Response, System Configured for Combo Fire/Mass Notification with Fire
Priority
If a fire alarm
only
occurs under this configuration, then the system will respond as in Section 4.4.3 above.
If a mass notification alarm/alert
only
occurs under this configuration, then the system will respond as in Section 4.4.7 above and addi-
tionally will:
• Signal the FACP of the alarm/alert using the FACP Data Bus such that the FACP can annunciate the alarm/alert and notify a
central station (if programmed to do so).
If a fire alarm is active in the system and a subsequent mass notification alarm/alert occurs, then the system will not respond until the fire
alarm has been restored.
4.4.10 Alarm/Alert Restoral, System Configured for Combo Fire/Mass Notification with Fire
Priority
If the restoral is for a fire alarm
only
under this configuration then the system will respond as in Section 4.4.4 above.
If the restoral is for a mass notification alarm/alert
only
under this configuration then the system will respond as in Section 4.4.8 above
and additionally will:
• Signal the FACP of the restoral using the FACP Data Bus such that the FACP can stop annunciation of the alarm/alert and notify
a central station (if programmed).
If the restoral is for a fire alarm that overrode an earlier active mass notification alarm/event then the system will:
• Stop playing the fire alarm message
• Turn the “Fire System Active” LED off
• Return the system to the active state of the earlier mass notification alarm/event
4.4.11 Alarm/Alert Response, System Configured for Combo Fire/Mass Notification with
Mass Notification Priority
If a fire alarm
only
occurs under this configuration then the system will respond as in Section 4.4.3 above.
If a mass notification alarm/alert
only
occurs under this configuration then the system will respond as in Section 4.4.7 above. and addi-
tionally will:
• Signal the FACP of the alarm/alert using the FACP Data Bus such that the FACP can annunciate the alarm/alert and notify a
central station (if programmed to do so).
If a fire alarm is active in the system and a subsequent mass notification alarm/alert occurs, then the system will:
• Stop playing the current fire message
• Signal the FACP of the alarm/alert using the FACP Data Bus such that the FACP can annunciate the alarm/alert, notify a central
station (if programmed), and turn off audible NACs (if programmed).
• Respond as in Section 4.4.7 above
If a mass notification alarm/alert is active in the system and a subsequent fire alarm occurs, then the system will not respond until the
mass notification alarm/alert is restored.
Summary of Contents for Notifier FirstCommand Series
Page 84: ...84 Notifier FirstCommand Series Manual P N LS10001 001NF E H 1 8 2018 Notes ...
Page 86: ...Cut along dotted line ...
Page 88: ...Cut along dotted line ...
Page 92: ...92 Notes ...
Page 94: ...Cut along dotted line ...
Page 96: ...NOTIFIER 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 www notifier com ...