Operating Power
Installation
2.3 Operating Power
2.3.1 AC Power and Earth Ground Connection
Primary power source for the NFC-50/100 is 120 VAC, 60 Hz, 3.5 amps. Primary power source for the NFC-50/100E is 240 VAC, 50
Hz, 2.0 amps. Over-current protection for this circuit must comply with Article 760 of the National Electrical Code (NEC) and/or local
codes. Make certain that the AC mains circuit breaker is off before making any wiring connections between the mains and the panel.
Connect AC mains wiring from the protected premises main breaker box to TB15 of the main control board. Use 14 AWG (2.0 mm2, 1.6
mm O.D.) or heavier gauge wire with 600V insulation. No other equipment may be connected to this circuit and it may not contain any
power disconnect devices. A separate Earth Ground connection must be made to ensure proper panel operation and lightning and tran-
sient protection. Do not use conduit for the Earth Ground connection since this does not provide reliable protection. Remove the two
keps nuts from the grounding stud in the backbox. Connect the incoming earth ground wire to supplied cable #71073 with a wire nut.
Position the ring terminal end over the grounding stud. Secure with one of the keps nuts. Place the ring terminal from the other supplied
Figure 2.5 NFC-50/100 Backbox Dimensions
n
fc-cab.
wm
f
Left Side
Right Side
Bottom
Door
Door
Backbox
Backbox
Depth =
Depth
Top
!
WARNING: RISK OF EQUIPMENT DAMAGE AND PERSONAL INJURY
SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL. DISCONNECT ALL SOURCES
OF POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING
AND/OR INSERTING CARDS, MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED. BE
SURE TO OBSERVE PROPER GROUNDING AND HANDLING PROCEDURES.
Summary of Contents for Notifier FirstCommand Series
Page 84: ...84 Notifier FirstCommand Series Manual P N LS10001 001NF E H 1 8 2018 Notes ...
Page 86: ...Cut along dotted line ...
Page 88: ...Cut along dotted line ...
Page 92: ...92 Notes ...
Page 94: ...Cut along dotted line ...
Page 96: ...NOTIFIER 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 www notifier com ...