Main Menu - User Programming
Programming
3.2.2 General/NAC Options
General Options
Unit Operation
Select whether the NFC will function for
Fire Evacuation
,
Mass Notification
, or a
Combination
of both.
Event Priority
When
Combo
or
Mass Notification
is selected for Unit Operation, select whether
Mass Notification
events or
Fire Evac-
uation
events will take priority in the system. If
Mass Notification
is selected as the Unit Operation with the Event Priority set to
Fire
Evacuation
, the NFC will be a mass notification only system but will allow the FACP to override it if a fire alarm sounds. If
Mass Noti-
fication
is selected as the Unit Operation with the Event Priority also set to
Mass Notification
, the NFC will not have any fire evacuation
capabilities and will report mass notification events to the FACP. In this configuration, FACP outputs can be turned off for mass notifica-
tion events if desired.
FACP Data Bus Control
If an FACP will directly communicate with the NFC, select which communication protocol will be used,
ACS-
Bus
or
ANN-Bus
.
FACP Data Bus Address
This field has no effect on programming and is used for informational purposes only.
When using the FACP
ACS-bus protocol, address
01
must be enabled in the FACP programming. When using the ANN-Bus protocol, the FACP will automati-
cally detect the audio system connection during annunciator auto-configuration. No ANN-Bus address selection is necessary at the
FACP. Enter the NFC’s address (1-8) here. If FACP control of the NFC is not selected, enter
0
.
24 Hour Resound
As
enabled
(default), the 24 Hour Resound feature causes the piezo on the NFC to sound a reminder ‘beep’ for
alarms and troubles after the panel has been silenced.
Canadian Configuration
Selecting
enable
will configure the panel to comply with Canadian requirements. See Appendix C for more
information.
Class A / Style Z
Select
enable
if all circuits on the NFC will operate in Class A (Style Z) or
disabled
if all circuits will operate in Class
B (Style Y).
Canadian Isolator Modules
If audio isolator modules are required in the system, select
enabled
. Refer to “Audio Room Isolator Mod-
ules” on page 83 for more information.
AC Loss Delay
The reporting of a loss of AC power using the AC Loss relay output can be delayed by programming the length of the
desired delay. The factory default setting is 2 hours. Options are
0, 2, 6, 12,
or
23
hours.
Secondary Amplifier
if an NFC-BDA-25/70V is installed, select whether it will be used as a
backup
amplifier or for
secondary
speaker
circuits. If an NFC-BDA-25/70V is not installed, select
none
.
Primary Amp 70 VAC
This field has no effect on programming and is used for informational purposes only.
The system can be con-
verted from 25V to 70V by installing the NFC-XRM-70V. If this transformer has been installed, be sure that SW5 on the main control
board has been set to “70V” operation. Use this field to record the amplifier’s settings.
Secondary Amp 70 VAC
This field has no effect on programming and is used for informational purposes only.
When the NFC-XRM-
70V has been installed and a secondary amplified is required, model number NFC-BDA-70V must be used. Use this field to record
which model has been installed in the system.
External Audio Input
If there is a permanent connection to TB5 on the display board, select whether the external audio input will func-
tion as
Background Music
or
External Paging - Night Ring
. See Section 4.4.15 for more information.
IP Address
The default IP address of 169.254.3.3 can be changed to another address with numbers from 0-255. Changing the IP address
is suggested for a higher level of security on the system’s programming. This number should be written down and stored in a safe loca-
tion.
Identification
Enter a label for this NFC system. Up to 80 character may be entered.
Figure 3.3 General Options
g
e
n
e
ra
lo
p
2
.j
p
g
Summary of Contents for Notifier FirstCommand Series
Page 84: ...84 Notifier FirstCommand Series Manual P N LS10001 001NF E H 1 8 2018 Notes ...
Page 86: ...Cut along dotted line ...
Page 88: ...Cut along dotted line ...
Page 92: ...92 Notes ...
Page 94: ...Cut along dotted line ...
Page 96: ...NOTIFIER 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 www notifier com ...