SERVO MOTORS FOR AIR DAMPERS AND BUTTERFLY VALVES

MT4000 Series

INSTRUCTION SHEET

EN

2C-0035SZ20 R0604

APPLICATION

The MT4000, MT4001, MT4002 and MT4003 are servo
motors to control and govern air lock of gaseous and liquid
fuels.
The servo motors are suitable in burners with small to
medium capacity.

SPECIFICATIONS

Models

MT4000A series for combustion air dampers and VF5000
butterfly valves. External signals for modulation required.
MT4000B series for combustion air dampers and VF5000
butterfly valves. Including relay for one external modulation
input.
MT4001A series for air dampers in gas burners. To be used
with full featured ignition controllers and 3 wire thermostats.
MT4001B series for air dampers in gas burners. To be used
with full featured ignition controllers and 2 wire thermostats.
MT4001C series can be used with satronic TMG740. The
ignition controller is providing the burner sequence, including
the drive to high fire during pre--purge.
MT4002B series for air dampers in oil burners. Including relay
for 2 wire thermostat connection.
MT4003C series can be used with standard low featured
ON/OFF ignition controllers,where the pre--purge is provided
by the servomotor. Including relays for 2 wire thermostat
connection, low fire adjustment switch and fail safe pre--purge
timer.

Dimensions

See Fig. 1. Installation drawing MT4000 Series

Supply voltage

Line voltage:

220 ... 240 Vac, 50/60 Hz
110 Vac, 50/60 Hz

Maximum voltage

Current of micro--switches: 250 Vac, 10A (ac) and 2A(dc)

Ambient temperature range

--15 ... 60

°

C

Relative humidity: 0 -- 90% at 40

o

C (non--condensing)

Rated torque value

Maximum torque at 6s rotation time over 90 degrees: 1.5 Nm
Maximum torque at 12s rotation time over 90 degrees: 1.5 Nm
Maximum torque at 24s rotation time over 90 degrees: 3.0 Nm

Maximum diagonal force

300N, when mounted with 4 screws

Stroke timing over 90 degrees

6, 12, 24 and 30 s at 50 Hz
At 60 Hz, the timing is reduced with approximately 20%

Maximum adjustable stroke

0 to 160 degrees

Enclosure

IP40

Minimum camshaft step

2 degrees (including mechanical tolerances)

Electrical connection

Two PG9 wiring conduits are provided in the housing.

NOTE: Do not provide strain--relief according to

EN60730

Finish

The servo motor is mounted in a black housing and
transparent plastic cover, which can be removed by loosening
2 screws.

Pre--purge timer (MT4003C only)

20 seconds, tolerance --0 s, +10 s.

Design life

Model

Number of Cycles

All models

MT4000

Series

250.000

Standards and approvals

The MT4000 Series conform with the folowing EC directives:

Low Voltage Directive (73/23/EEC)
PIN: 0063AR1582

Electro Magnetic Compatibility Directive (89/336/EEC)

EN298 for MT4003C with pre--purge timer

Summary of Contents for MT4000 Series

Page 1: ...ection low fire adjustment switch and fail safe pre purge timer Dimensions See Fig 1 Installation drawing MT4000 Series Supply voltage Line voltage 220 240 Vac 50 60 Hz 110 Vac 50 60 Hz Maximum voltage Current of micro switches 250 Vac 10A ac and 2A dc Ambient temperature range 15 60 C Relative humidity 0 90 at 40 oC non condensing Rated torque value Maximum torque at 6s rotation time over 90 degr...

Page 2: ...er motor II closed position of air damper motor III auxiliary switches III low fire position of air damper motor IV auxiliary switches IV low fire position of air damper motor V switches the second stage operation of the gas valves Adjustment for cams Disconnect power supply and remove the cover Use adjustment tool inside the cover to adjust the cams Place the tool in one of the cam grooves to tur...

Page 3: ...ry set at 0 degrees to start the air damper in closed position II Factory set at 0 degrees to start the air damper in closed position III IV Rotate cam clockwise to increase the low fire position of air damper Rotate cam counter clockwise to decrease the low fire position of the air damper III IV Rotate cam counter clockwise to increase the low fire position of air damper Rotate cam clockwise to d...

Page 4: ... low drive signal power signal during run 1 Fig 7 Wiring diagram MT4001C input main valve neutral fan input line output main valve 2 3 4 5 6 7 8 9 fan output Tmod 1 Fig 8 Wiring Diagram MT4002B input main valve fan input neutral line output main valve 2 3 4 5 6 7 8 9 Tmod power signal during run 1 Fig 9 Wiring diagram MT4003C Control Product Satronic AG Honeywell Platz 1 CH 8157 Dielsdorf Switzerl...

Reviews: