background image

EN2C-0035SZ20 R0604                                                                             

2

INSTALLATION

IMPORTANT

1. Installer must be a trained experienced service

man.

2. Disconnect power supply to prevent electrical

shock and/or equipment damage.

3. When the MT4000 is used in stand alone

applications, use a proper strain--relief

4. The appliance manufacturer’s instructions should

be followed when provided.

5. Carry out a thorough checkout when installation is

completed.

Low fire adjustment switch
(optional)

0

Fig. 1. Installation drawing MT4000 Series

Mounting and orientation

There are no restrictions in the mounting angle of the motor.
The motor can be assembled by 4 screws. For mounting hole
dimensions, see installation drawing.

ADJUSTMENT AND CHECKOUT

WARNING

Adjustment should be made by qualified personnel only.

If the appliance manufacturer supplies checkout and/or
service and maintenance instructions, carefully follow
them.

All adjustments on the cams should be done

after

disconnecting the power supply.

Functions of cams:

MT4000 A/B series

MT4001 A/B/C, MT4002B

& MT4003C series

cam

cam

I

high fire position of
air damper motor

I

high fire position of
air damper motor

II

closed position of
the air damper motor

II

closed position of air
damper motor

III

auxiliary switches

III

low fire position of air
damper motor

IV

auxiliary switches

IV

low fire position of air
damper motor

V

switches the second
stage operation of
the gas valves

Adjustment for cams

Disconnect power supply and remove the cover. Use
adjustment tool inside the cover to adjust the cams. Place the
tool in one of the cam grooves to turn the cam in steps of
approximately 2 degrees.

Factory set “zero position”

All motors are factory set with zero position corresponding
with 45 degrees angle of flat surface on actuator shaft (see
figure 1.).
When field re--adjustment of zero position is necessary, rotate
cam II (clock or counter--clockwise) to zero position and
re--adjust arrow on scale manually.

Low fire adjustment switch (optional)

A push button switch, to activate electrically movement of the
cam assembly, independent from the flame relay signals, is
optional on MT4001B, MT4001C, MT4002B and MT4003C
type of servo motors.
Use the push button switch to move the cam assembly
forward during (re)adjustment of the low fire position of the
damper. When this push button is pressed down, the motor
will drive to high fire position. When the push button is
released, the motor will drive to low fire position.
Depending on type, it is positioned either on left or right side
of the front plate.

Summary of Contents for MT4000 Series

Page 1: ...ection low fire adjustment switch and fail safe pre purge timer Dimensions See Fig 1 Installation drawing MT4000 Series Supply voltage Line voltage 220 240 Vac 50 60 Hz 110 Vac 50 60 Hz Maximum voltage Current of micro switches 250 Vac 10A ac and 2A dc Ambient temperature range 15 60 C Relative humidity 0 90 at 40 oC non condensing Rated torque value Maximum torque at 6s rotation time over 90 degr...

Page 2: ...er motor II closed position of air damper motor III auxiliary switches III low fire position of air damper motor IV auxiliary switches IV low fire position of air damper motor V switches the second stage operation of the gas valves Adjustment for cams Disconnect power supply and remove the cover Use adjustment tool inside the cover to adjust the cams Place the tool in one of the cam grooves to tur...

Page 3: ...ry set at 0 degrees to start the air damper in closed position II Factory set at 0 degrees to start the air damper in closed position III IV Rotate cam clockwise to increase the low fire position of air damper Rotate cam counter clockwise to decrease the low fire position of the air damper III IV Rotate cam counter clockwise to increase the low fire position of air damper Rotate cam clockwise to d...

Page 4: ... low drive signal power signal during run 1 Fig 7 Wiring diagram MT4001C input main valve neutral fan input line output main valve 2 3 4 5 6 7 8 9 fan output Tmod 1 Fig 8 Wiring Diagram MT4002B input main valve fan input neutral line output main valve 2 3 4 5 6 7 8 9 Tmod power signal during run 1 Fig 9 Wiring diagram MT4003C Control Product Satronic AG Honeywell Platz 1 CH 8157 Dielsdorf Switzerl...