Installing the MPA2 Panels
Installation
MPA2 Access Control Unit Installation Guide, Document 800-25395 - B
23
Warning:
MPA2 reader connections are using CAT 6E/7 (S)/FTP cable
with RJ45 connections. Be aware that this is NOT an
Internet/Ethernet protocol and so should not be mixed or connected
to standard Ethernet Network devices as switches or routers.
Note:
Dip switch 1 to 4 should be OFF for Wiegand in S1. For SW1, Wiegand
1 and 10 should be OFF and OSDP 1 and 10 should be ON.
Figure 5: Wiring of Multiple Readers to the Controller Board (DOOR 1)
Warning:
MPA2 reader connections are using CAT 6E/7 (S)/FTP cable
with RJ45 connections. Be aware that this is NOT an
Internet/Ethernet protocol and so should not be mixed or connected
to standard Ethernet Network devices as switches or routers.
The following three tables list the factory controller board I/O default
settings for door-1 and door-2 configurations. These are the mappings for