M7161, M7164, M7184
SPECIFICATIONS • ORDERING INFORMATION

Specifications

MODELS:

M71 6 1 A,B,G
M71 6 4 A,B,G
M71 8 4 A

Control Type

Suffix Letter

71

 is dc voltage input

A:

is fixed stroke

0.8-3.3, 4-7, 6-9 or

(90

°

 or 160

°

), electrically

10.5-13.5 Vdc

normally closed,
no auxiliary switches.

Power Rating

B:

is fixed stroke

6

is low power—

(90

°

 or 160

°

), electrically

35 lb-in. torque

normally closed,

8

is high power—

1 auxiliary switch.

150 lb-in. torque

G:

is fixed stroke
(90

°

 or 160

°

), electrically

normally open,
no auxiliary switches.

Output Drive
4

is dual-ended shaft, nonspring return.

1

is single-ended shaft, nonspring return.

MOTOR ROTATION:

Normally closed M7161A,B and M7164A,B; M7184A

drives to fully counterclockwise  

(as viewed

from the power end) to the fully closed position when
powered input signal is at a minimum.

Electrically normally open M7161G and M7164G drive

clockwise

(as viewed from the power end) to

the fully open position when the powered input signal
is at a minimum.

STROKE: Fixed 90

°

 or 160

°

 stroke models available.

TIMING: Nominal 30 seconds for 90

°

 stroke and 60 seconds

for 160

°

 stroke.

DEAD WEIGHT LOAD ON SHAFT:

MAXIMUM DAMPER RATING:

M7161A,B,G and M7164A,B,G: B dimension = 48 in.
M7184A: B dimension = 202 in.

AMBIENT TEMPERATURE RATINGS:

Maximum: 150

°

 F [66

°

 C] at 25% duty cycle.

Minimum: -40

°

 F [-40

°

 C].

SHAFT: 3/8 in. [9.5 mm] square.

M7161 Models: Single-ended shaft.
M7164 and M7184 Models: Dual-ended shaft.

DIMENSIONS: See Fig. 1.
UNDERWRITERS LABORATORIES INC. LISTED:

File No. E4436, Guide No. XAPX.

CANADIAN STANDARDS ASSOCIATION CERTIFIED:

General Listing File No. LR1620, Guide 400-E.

ELECTRICAL RATINGS:

Voltage
Vac @

Current

Power Con-

50/60 Hz

Draw (A)

sumption (W)

M7161

24

0.62

14

M7164

120

0.20

19

M7184

24

0.80

18

AUXILIARY SWITCH RATINGS (Amperes):

One Contact
Rating

a

120V

240V

Full Load

7.2

3.6

Locked Rotor

43.2

21.6

a  

40 VA pilot duty, 120/240 Vac on opposite contact.

ACCESSORIES:

ES650117 Explosion-proof Housing: Encloses motor for

use in explosive atmospheres. Not for use with Q601,
Q618, and Q455 Linkages. Order separately from Nelson
Electric Co. Requires Honeywell 7616DM Coupling.

Q607 External Auxiliary Switch: Controls auxiliary equip-

ment as a function of motor position.

Ordering Information

When purchasing replacement and modernization products from your wholesaler or your distributor, refer to the price sheets for
complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:

1. Your local Honeywell Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Satisfaction

Honeywell Inc.,
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (612) 951-1000

In Canada—Honeywell Limited/Honeywell Limitée, 740 Ellesmere Road, Scarborough, Ontario M1P 2V9. International Sales
and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan,
Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

Power End

Auxiliary End

M7161

100 lb (45.4 kg)

N/A

M7164

100 lb (45.4 kg)

100 lb (45.4 kg)

M7184

200 lb (90.8 kg)

200 lb (90.8 kg)

300 lb (136.2 kg) maximum combined (power and auxil-

iary end) dead weight load.

Summary of Contents for M7161

Page 1: ...lectrically normally open all other motors are electrically normally closed Oil immersed motor and gear train for reliable performance and long life Wiring box provides NEMA 3 weather protection Actuator motor and circuitry operate from 24 Vac Models available with factory installed transformer or an internal transformer can be field added Quick connect terminals standard screw termi nal adapter a...

Page 2: ...SASSOCIATIONCERTIFIED General Listing File No LR1620 Guide 400 E ELECTRICAL RATINGS Voltage Vac Current Power Con 50 60 Hz Draw A sumption W M7161 24 0 62 14 M7164 120 0 20 19 M7184 24 0 80 18 AUXILIARY SWITCH RATINGS Amperes One Contact Ratinga 120V 240V Full Load 7 2 3 6 Locked Rotor 43 2 21 6 a 40 VA pilot duty 120 240 Vac on opposite contact ACCESSORIES ES650117 Explosion proof Housing Enclose...

Page 3: ...d Linkage Assembly Connects Modutrol Motor to water or steam valve Q5001 Valve Linkage Connects Modutrol Motor to water or steam valve Q100 Linkage Connects Modutrol Motor to butterfly valve 221455A Motor Crank Arm Infinitely adjustable crank arm Approximately 0 75 inch shorter than the 4074ELY Crank Arm can rotate through downward position and clear base of motor without requiring use of adapter ...

Page 4: ...4A B and M7184A Motors are ship ped from the factory in the closed position at the limit of counterclockwise rotation as viewed from the power end of the motor M7161G and M7164G are shipped in the open position atthelimitofclockwiserotationasviewedfromthe power end of the motor See Fig 2 ADAPTER BRACKET The 220738A Adapter Bracket positioned between the motor and the equipment raises the shaft hei...

Page 5: ...red distance while the motor moves through its full stroke 2 With modulating control maximum damper opening should be no more than 60 Little additional airflow is provided beyond this point 3 The motor must be stopped at the end of its stroke by the limit switch and must not be stalled by the damper or valve The motor will be damaged if it is not permitted to complete its full stroke 4 Do not exce...

Page 6: ... the motor correspond to the characteristics of the power supply See Figs 6 7 for typical system wiring Make certain that the voltage and frequency stamped on the transformer correspond to the characteristics of the power supply The motor terminals are quick connects located on top of theprintedcircuitboardshowninFig 5 Accesstothewiring compartment is gained by removing the four screws on the top ...

Page 7: ...ig 9 CAUTION 1 Live circuits are exposed during the auxiliary switch adjustment procedure Always turn off power before adjusting switch cams 2 Do not turn motor shaft by hand or with wrench as damage to the motor can result NOTE The following instructions are for normally closed motors motor shaft rotates clockwise as viewed from the power end of the motor on an increase in signal 1 Remove cover o...

Page 8: ...PROX 1 DIFF SLOW RISE PORTION APPROX 10 DIFF INNER AUXILIARY CAM BLUE SWITCH FOLLOWER C F R MOVE SCREWDRIVER AT TOP ONLY TO ADJUST CAM 1 8 IN STRAIGHT BLADE SCREWDRIVER RIGHT INNER AUXILIARY SWITCH SLOW RISE PORTION APPROX 10 DIFF INNER AUXILIARY CAM RED SWITCH FOLLOWER FAST RISE PORTION APPROX 1 DIFF L2 L1 HOT 1 2 1 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED TRANS...

Page 9: ... in 4 0 N m pushrod M7164G1030a e electrically normally openc M7164A1017a 90 deg 30 sec 24 Vac Q605 14W 35 lb in 4 0 N m pushrod electrically normally closedc 4 0 to 7 0 M7161G1017b e 90 deg 30 sec 120 Vac Q100 M7164G1014b e 19W 35 lb in 4 0 N m electrically normally openc M7161G1025d e 160 deg 60 sec 24 Vac Q601 Q618 M7164G1022d e 14W 35 lb in 4 0 N m or Q5001 electrically normally openc M7164A10...

Page 10: ...uator and connect to the motor according to Table 2 and Fig 11 M7161 M7164 M7184 OPERATION AND REPLACEMENT Fig 10 Replacing Ranco Linear Actuator with M7164 in a damper application Use linkage Q605 recommended and pushrod to change from a linear to a circular force CRANK ARM 221455A PUSH ROD NO 27520 C THRU L 90 DEGREE MOTOR BALL JOINT NO 27518 M 493A HONEYWELL RANCO TABLE 2 LA2 1000 2000 TO M7164...

Page 11: ... JumperterminalsCandF motorshoulddrivetothefully open clockwise positionasviewedfromthepower end Remove jumper Remove the lead from terminal C or R motor should drive to the closed fully counterclock wise position M7161G and M7164G JumperterminalsCandF motorshoulddrivefullclosed fullycounterclockwise positionasviewedfromthe power end Remove jumper Remove the lead from termi nal C or R motor should...

Page 12: ...nd Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley Minnesota 55422 Scarborough Ontario M1P 2V9 Printed in U S A QUALITY IS KEY ...

Reviews: