OPERATION

The M7161, M7164 and M7184 Motors operate in

response to a dc voltage input signal to terminals C and R,
positioning a valve or damper at any position between fully
open and fully closed. The input signal causes the modified
dc bridge circuit in the motor to become unbalanced. The
small signal resulting from the bridge unbalance is ampli-
fied and energizes 1 of 2 triacs to run the motor. As the motor
runs, a feedback potentiometer driven by the motor moves
to rebalance the bridge. When the bridge is balanced, the
motor stops.

REPLACEMENT OF RANCO LA2 LINEAR
ACTUATORS AND HONEYWELL SPECIAL
PACKAGED HVAC UNIT MOTORS

The M7164 Motors may be used for field replacement

of Ranco LA2-1000 Series Zone Mixing Damper Actuators
and LA2-2000 Series Modulating Heating Valve Actuators
as described below. To select the appropriate model, refer
to Table 1.

TABLE 1—CROSS REFERENCE OF RANCO AND HONEYWELL ELECTRONIC MOTORS.

Ranco

Input

Linkage

Actuator Family

Voltage dc

Honeywell Motor Replacement

Required

10.5 to 13.5

M7161G1009

a,e

90 deg, 30 sec, 120 Vac,

Q605,

M7164G1006

a,e

19W, 35 lb-in. [4.0 N-m],

pushrod

M7164G1030

a,e

electrically normally open

c

.

M7164A1017

a

90 deg, 30 sec, 24 Vac,

Q605,

14W, 35 lb-in. [4.0 N-m],

pushrod

electrically normally closed

c

.

4.0 to 7.0

M7161G1017

b,e

90 deg, 30 sec, 120 Vac,

Q100

M7164G1014

b,e

19W, 35 lb-in. [4.0 N-m],
electrically normally open

c

.

M7161G1025

d,e

160 deg, 60 sec, 24 Vac,

Q601, Q618

M7164G1022

d,e

14W, 35 lb-in. [4.0 N-m],

or Q5001

electrically normally open

c

.

M7164A1009

d

160 deg, 60 sec, 24 Vac,

Q601, Q618

19W, 35 lb-in. [4.0 N-m],

or Q5001

electrically normally closed

c

.

a

New damper linkage and pushrod required.

b

This motor is used with modulating gas valves (butterfly valves).

c

On the Ranco Actuator, 

electrical normal

 is the position (extended = open; retracted = closed) of the actuator drive shaft (as

viewed from the power end) when power is applied to the motor and input (command) signal is at the lowest point of the input
voltage range.

d

These motors are for use with modulating steam or hot water valves: valve and linkage replacement are required.

e

This normally open motor provides 

power end

 damper linkage connection when space constraints prevent using a normally

closed motor.

LA2-1000
Zone Mixing
Damper Actuator
direct-action,
spring return,
nominal 35 lb
[155.6N] force,
2 in.[50.8 mm]
stroke.

LA2-2000
Modulating Heating
Valve Actuator
reverse-acting,
spring return,
nominal 35 lb
[155.6 N] force,
2 in. [50.8 mm]
stroke.

Summary of Contents for M7161

Page 1: ...lectrically normally open all other motors are electrically normally closed Oil immersed motor and gear train for reliable performance and long life Wiring box provides NEMA 3 weather protection Actuator motor and circuitry operate from 24 Vac Models available with factory installed transformer or an internal transformer can be field added Quick connect terminals standard screw termi nal adapter a...

Page 2: ...SASSOCIATIONCERTIFIED General Listing File No LR1620 Guide 400 E ELECTRICAL RATINGS Voltage Vac Current Power Con 50 60 Hz Draw A sumption W M7161 24 0 62 14 M7164 120 0 20 19 M7184 24 0 80 18 AUXILIARY SWITCH RATINGS Amperes One Contact Ratinga 120V 240V Full Load 7 2 3 6 Locked Rotor 43 2 21 6 a 40 VA pilot duty 120 240 Vac on opposite contact ACCESSORIES ES650117 Explosion proof Housing Enclose...

Page 3: ...d Linkage Assembly Connects Modutrol Motor to water or steam valve Q5001 Valve Linkage Connects Modutrol Motor to water or steam valve Q100 Linkage Connects Modutrol Motor to butterfly valve 221455A Motor Crank Arm Infinitely adjustable crank arm Approximately 0 75 inch shorter than the 4074ELY Crank Arm can rotate through downward position and clear base of motor without requiring use of adapter ...

Page 4: ...4A B and M7184A Motors are ship ped from the factory in the closed position at the limit of counterclockwise rotation as viewed from the power end of the motor M7161G and M7164G are shipped in the open position atthelimitofclockwiserotationasviewedfromthe power end of the motor See Fig 2 ADAPTER BRACKET The 220738A Adapter Bracket positioned between the motor and the equipment raises the shaft hei...

Page 5: ...red distance while the motor moves through its full stroke 2 With modulating control maximum damper opening should be no more than 60 Little additional airflow is provided beyond this point 3 The motor must be stopped at the end of its stroke by the limit switch and must not be stalled by the damper or valve The motor will be damaged if it is not permitted to complete its full stroke 4 Do not exce...

Page 6: ... the motor correspond to the characteristics of the power supply See Figs 6 7 for typical system wiring Make certain that the voltage and frequency stamped on the transformer correspond to the characteristics of the power supply The motor terminals are quick connects located on top of theprintedcircuitboardshowninFig 5 Accesstothewiring compartment is gained by removing the four screws on the top ...

Page 7: ...ig 9 CAUTION 1 Live circuits are exposed during the auxiliary switch adjustment procedure Always turn off power before adjusting switch cams 2 Do not turn motor shaft by hand or with wrench as damage to the motor can result NOTE The following instructions are for normally closed motors motor shaft rotates clockwise as viewed from the power end of the motor on an increase in signal 1 Remove cover o...

Page 8: ...PROX 1 DIFF SLOW RISE PORTION APPROX 10 DIFF INNER AUXILIARY CAM BLUE SWITCH FOLLOWER C F R MOVE SCREWDRIVER AT TOP ONLY TO ADJUST CAM 1 8 IN STRAIGHT BLADE SCREWDRIVER RIGHT INNER AUXILIARY SWITCH SLOW RISE PORTION APPROX 10 DIFF INNER AUXILIARY CAM RED SWITCH FOLLOWER FAST RISE PORTION APPROX 1 DIFF L2 L1 HOT 1 2 1 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED TRANS...

Page 9: ... in 4 0 N m pushrod M7164G1030a e electrically normally openc M7164A1017a 90 deg 30 sec 24 Vac Q605 14W 35 lb in 4 0 N m pushrod electrically normally closedc 4 0 to 7 0 M7161G1017b e 90 deg 30 sec 120 Vac Q100 M7164G1014b e 19W 35 lb in 4 0 N m electrically normally openc M7161G1025d e 160 deg 60 sec 24 Vac Q601 Q618 M7164G1022d e 14W 35 lb in 4 0 N m or Q5001 electrically normally openc M7164A10...

Page 10: ...uator and connect to the motor according to Table 2 and Fig 11 M7161 M7164 M7184 OPERATION AND REPLACEMENT Fig 10 Replacing Ranco Linear Actuator with M7164 in a damper application Use linkage Q605 recommended and pushrod to change from a linear to a circular force CRANK ARM 221455A PUSH ROD NO 27520 C THRU L 90 DEGREE MOTOR BALL JOINT NO 27518 M 493A HONEYWELL RANCO TABLE 2 LA2 1000 2000 TO M7164...

Page 11: ... JumperterminalsCandF motorshoulddrivetothefully open clockwise positionasviewedfromthepower end Remove jumper Remove the lead from terminal C or R motor should drive to the closed fully counterclock wise position M7161G and M7164G JumperterminalsCandF motorshoulddrivefullclosed fullycounterclockwise positionasviewedfromthe power end Remove jumper Remove the lead from termi nal C or R motor should...

Page 12: ...nd Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley Minnesota 55422 Scarborough Ontario M1P 2V9 Printed in U S A QUALITY IS KEY ...

Reviews: