M7161, M7164, M7184

INSTALLATION

5

63-2197—2

applications requiring the crank arm to rotate through the
bottom plane of the actuator. If the bracket is not used in a
replacement application, the damper linkage must be ad-
justed to the new shaft position.

 The motor comes without a crank arm. The crank arm is

included in the Q605 Linkage or may be ordered separately
(see Accessories).

For detailed instructions on the assembly of specific

linkages, refer to the instructions packed with each linkage.
In general, however, check the following points of operation
when installing a motor and linkage:

1. Linkages for valves and louver type dampers should

be adjusted so that the damper or valve moves through only

the maximum required distance while the motor moves
through its full stroke.

2. With modulating control, maximum damper opening

should be no more than 60

°

. Little additional airflow is

provided beyond this point.

3. The motor must be stopped at the end of its stroke by

the limit switch and must not be stalled by the damper or
valve. The motor will be damaged if it is not permitted to
complete its full stroke.

4. Do not exceed the motor ratings in any installation.
5. Do not turn motor shaft manually or with a wrench—

this will damage the motor.

Fig. 3—Mounting motor with an adapter bracket. The bracket is first mounted to the equipment with standard
bolts. The motor is then mounted to the bracket using the bolts provided that thread into the bracket holes.

EQUIPMENT

BASE

ADAPTER

BRACKET

STANDARD

BOLTS (4)

M307G

WIRING BOX

BOLTS 

PROVIDED (4)

MOTOR

POWER

END

1    NO. 12 OR 1/4 IN. ZINC PLATED MACHINE SCREWS OR BOLTS.

1

POWER END

POWER END

Summary of Contents for M7161

Page 1: ...lectrically normally open all other motors are electrically normally closed Oil immersed motor and gear train for reliable performance and long life Wiring box provides NEMA 3 weather protection Actuator motor and circuitry operate from 24 Vac Models available with factory installed transformer or an internal transformer can be field added Quick connect terminals standard screw termi nal adapter a...

Page 2: ...SASSOCIATIONCERTIFIED General Listing File No LR1620 Guide 400 E ELECTRICAL RATINGS Voltage Vac Current Power Con 50 60 Hz Draw A sumption W M7161 24 0 62 14 M7164 120 0 20 19 M7184 24 0 80 18 AUXILIARY SWITCH RATINGS Amperes One Contact Ratinga 120V 240V Full Load 7 2 3 6 Locked Rotor 43 2 21 6 a 40 VA pilot duty 120 240 Vac on opposite contact ACCESSORIES ES650117 Explosion proof Housing Enclose...

Page 3: ...d Linkage Assembly Connects Modutrol Motor to water or steam valve Q5001 Valve Linkage Connects Modutrol Motor to water or steam valve Q100 Linkage Connects Modutrol Motor to butterfly valve 221455A Motor Crank Arm Infinitely adjustable crank arm Approximately 0 75 inch shorter than the 4074ELY Crank Arm can rotate through downward position and clear base of motor without requiring use of adapter ...

Page 4: ...4A B and M7184A Motors are ship ped from the factory in the closed position at the limit of counterclockwise rotation as viewed from the power end of the motor M7161G and M7164G are shipped in the open position atthelimitofclockwiserotationasviewedfromthe power end of the motor See Fig 2 ADAPTER BRACKET The 220738A Adapter Bracket positioned between the motor and the equipment raises the shaft hei...

Page 5: ...red distance while the motor moves through its full stroke 2 With modulating control maximum damper opening should be no more than 60 Little additional airflow is provided beyond this point 3 The motor must be stopped at the end of its stroke by the limit switch and must not be stalled by the damper or valve The motor will be damaged if it is not permitted to complete its full stroke 4 Do not exce...

Page 6: ... the motor correspond to the characteristics of the power supply See Figs 6 7 for typical system wiring Make certain that the voltage and frequency stamped on the transformer correspond to the characteristics of the power supply The motor terminals are quick connects located on top of theprintedcircuitboardshowninFig 5 Accesstothewiring compartment is gained by removing the four screws on the top ...

Page 7: ...ig 9 CAUTION 1 Live circuits are exposed during the auxiliary switch adjustment procedure Always turn off power before adjusting switch cams 2 Do not turn motor shaft by hand or with wrench as damage to the motor can result NOTE The following instructions are for normally closed motors motor shaft rotates clockwise as viewed from the power end of the motor on an increase in signal 1 Remove cover o...

Page 8: ...PROX 1 DIFF SLOW RISE PORTION APPROX 10 DIFF INNER AUXILIARY CAM BLUE SWITCH FOLLOWER C F R MOVE SCREWDRIVER AT TOP ONLY TO ADJUST CAM 1 8 IN STRAIGHT BLADE SCREWDRIVER RIGHT INNER AUXILIARY SWITCH SLOW RISE PORTION APPROX 10 DIFF INNER AUXILIARY CAM RED SWITCH FOLLOWER FAST RISE PORTION APPROX 1 DIFF L2 L1 HOT 1 2 1 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED TRANS...

Page 9: ... in 4 0 N m pushrod M7164G1030a e electrically normally openc M7164A1017a 90 deg 30 sec 24 Vac Q605 14W 35 lb in 4 0 N m pushrod electrically normally closedc 4 0 to 7 0 M7161G1017b e 90 deg 30 sec 120 Vac Q100 M7164G1014b e 19W 35 lb in 4 0 N m electrically normally openc M7161G1025d e 160 deg 60 sec 24 Vac Q601 Q618 M7164G1022d e 14W 35 lb in 4 0 N m or Q5001 electrically normally openc M7164A10...

Page 10: ...uator and connect to the motor according to Table 2 and Fig 11 M7161 M7164 M7184 OPERATION AND REPLACEMENT Fig 10 Replacing Ranco Linear Actuator with M7164 in a damper application Use linkage Q605 recommended and pushrod to change from a linear to a circular force CRANK ARM 221455A PUSH ROD NO 27520 C THRU L 90 DEGREE MOTOR BALL JOINT NO 27518 M 493A HONEYWELL RANCO TABLE 2 LA2 1000 2000 TO M7164...

Page 11: ... JumperterminalsCandF motorshoulddrivetothefully open clockwise positionasviewedfromthepower end Remove jumper Remove the lead from terminal C or R motor should drive to the closed fully counterclock wise position M7161G and M7164G JumperterminalsCandF motorshoulddrivefullclosed fullycounterclockwise positionasviewedfromthe power end Remove jumper Remove the lead from termi nal C or R motor should...

Page 12: ...nd Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley Minnesota 55422 Scarborough Ontario M1P 2V9 Printed in U S A QUALITY IS KEY ...

Reviews: