Honeywell M7161 Manual Download Page 11

11

63-2197—2

Fig. 11—Wiring for replacement of Ranco LA2-1000/2000 Series Actuators with Honeywell 24V M7164A,G.

M7161, M7164, M7184

OPERATION AND REPLACEMENT  •  CHECKOUT

POWER SUPPLY.  PROVIDE OVERLOAD PROTECTION AND DIS-
CONNECT MEANS AS REQUIRED.

SOLID LINES (       ) ARE EXISTING CONNECTIONS.  DASHED LINES
 (            ) ARE NEW CONNECTIONS.  "X'S" INDICATE REMOVAL OF
 EXISTING WIRING.

CONNECTIONS SHOWN ARE FOR 24V MOTORS.  MODELS WITH 
L1, L2 TERMINALS REQUIRE NEW 120V POWER SUPPLY WIRING
 

M3006

LA1-1000/2000

SERIES

ACTUATORS

(ZONE)

COMD(+)

REF(  )

24 VAC

24 VAC

L1

(HOT)

L2

1

L1

(HOT)

L2

1

3

R

C

T1

T2

TRANSFORMER

EA3

TR-3 ZONE
THERMOSTAT

ZONE
DISCHARGE
SENSOR

TR1

TRANSFORMER

TO OTHER
ZONE 
TR3/TR4

MOTOR

2

1

1

6

9

10

3

1 2 3 4 5 6 HI  L0 7 8 9 10 11 12

2

5

4

1

3

C

3

H

3

C

2

H

2

H

1

C

1

24 VAC

24VDC 

+

TO OTHER
ZONE 
TR3/TR4

ZONE

ZONE

2
3
4
5
6

12
11
10

9
8
7

ZONES

LOAD ANALYZER MODULE

L1

L 2

F

Checkout

MOTOR OPERATION CHECK

M7161A,B, M7164A,B and M7184A

Jumper terminals C and F; motor should drive to the fully

open (clockwise

) position as viewed from the power

end. Remove jumper. Remove the lead from terminal C or
R; motor should drive to the closed (fully counterclock-
wise

) position.

M7161G and M7164G

Jumper terminals C and F; motor should drive full closed

(fully counterclockwise

position as viewed from the

power end). Remove jumper. Remove the lead from termi-
nal C or R; motor should drive to the open (fully clock-
wise

) position.

After installation and linkage adjustment, operate the

motor through the thermostat or panel. Make sure that:

• The motor operates the damper or valve properly.
• The motor responds properly as input voltage is varied.
• The auxiliary switch, if used, operates at the desired

point of motor rotation.

Inspect the motor, linkage, and valve or damper to see that

all mechanical connections are correct and secure. In damper
installations, the pushrod should not extend more than a few
inches past the ball joints. Check to see that there is adequate
clearance for the linkage to move through its stroke without
binding or striking other objects. See System Instructions for
additional checkout procedures.

Summary of Contents for M7161

Page 1: ...lectrically normally open all other motors are electrically normally closed Oil immersed motor and gear train for reliable performance and long life Wiring box provides NEMA 3 weather protection Actuator motor and circuitry operate from 24 Vac Models available with factory installed transformer or an internal transformer can be field added Quick connect terminals standard screw termi nal adapter a...

Page 2: ...SASSOCIATIONCERTIFIED General Listing File No LR1620 Guide 400 E ELECTRICAL RATINGS Voltage Vac Current Power Con 50 60 Hz Draw A sumption W M7161 24 0 62 14 M7164 120 0 20 19 M7184 24 0 80 18 AUXILIARY SWITCH RATINGS Amperes One Contact Ratinga 120V 240V Full Load 7 2 3 6 Locked Rotor 43 2 21 6 a 40 VA pilot duty 120 240 Vac on opposite contact ACCESSORIES ES650117 Explosion proof Housing Enclose...

Page 3: ...d Linkage Assembly Connects Modutrol Motor to water or steam valve Q5001 Valve Linkage Connects Modutrol Motor to water or steam valve Q100 Linkage Connects Modutrol Motor to butterfly valve 221455A Motor Crank Arm Infinitely adjustable crank arm Approximately 0 75 inch shorter than the 4074ELY Crank Arm can rotate through downward position and clear base of motor without requiring use of adapter ...

Page 4: ...4A B and M7184A Motors are ship ped from the factory in the closed position at the limit of counterclockwise rotation as viewed from the power end of the motor M7161G and M7164G are shipped in the open position atthelimitofclockwiserotationasviewedfromthe power end of the motor See Fig 2 ADAPTER BRACKET The 220738A Adapter Bracket positioned between the motor and the equipment raises the shaft hei...

Page 5: ...red distance while the motor moves through its full stroke 2 With modulating control maximum damper opening should be no more than 60 Little additional airflow is provided beyond this point 3 The motor must be stopped at the end of its stroke by the limit switch and must not be stalled by the damper or valve The motor will be damaged if it is not permitted to complete its full stroke 4 Do not exce...

Page 6: ... the motor correspond to the characteristics of the power supply See Figs 6 7 for typical system wiring Make certain that the voltage and frequency stamped on the transformer correspond to the characteristics of the power supply The motor terminals are quick connects located on top of theprintedcircuitboardshowninFig 5 Accesstothewiring compartment is gained by removing the four screws on the top ...

Page 7: ...ig 9 CAUTION 1 Live circuits are exposed during the auxiliary switch adjustment procedure Always turn off power before adjusting switch cams 2 Do not turn motor shaft by hand or with wrench as damage to the motor can result NOTE The following instructions are for normally closed motors motor shaft rotates clockwise as viewed from the power end of the motor on an increase in signal 1 Remove cover o...

Page 8: ...PROX 1 DIFF SLOW RISE PORTION APPROX 10 DIFF INNER AUXILIARY CAM BLUE SWITCH FOLLOWER C F R MOVE SCREWDRIVER AT TOP ONLY TO ADJUST CAM 1 8 IN STRAIGHT BLADE SCREWDRIVER RIGHT INNER AUXILIARY SWITCH SLOW RISE PORTION APPROX 10 DIFF INNER AUXILIARY CAM RED SWITCH FOLLOWER FAST RISE PORTION APPROX 1 DIFF L2 L1 HOT 1 2 1 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED TRANS...

Page 9: ... in 4 0 N m pushrod M7164G1030a e electrically normally openc M7164A1017a 90 deg 30 sec 24 Vac Q605 14W 35 lb in 4 0 N m pushrod electrically normally closedc 4 0 to 7 0 M7161G1017b e 90 deg 30 sec 120 Vac Q100 M7164G1014b e 19W 35 lb in 4 0 N m electrically normally openc M7161G1025d e 160 deg 60 sec 24 Vac Q601 Q618 M7164G1022d e 14W 35 lb in 4 0 N m or Q5001 electrically normally openc M7164A10...

Page 10: ...uator and connect to the motor according to Table 2 and Fig 11 M7161 M7164 M7184 OPERATION AND REPLACEMENT Fig 10 Replacing Ranco Linear Actuator with M7164 in a damper application Use linkage Q605 recommended and pushrod to change from a linear to a circular force CRANK ARM 221455A PUSH ROD NO 27520 C THRU L 90 DEGREE MOTOR BALL JOINT NO 27518 M 493A HONEYWELL RANCO TABLE 2 LA2 1000 2000 TO M7164...

Page 11: ... JumperterminalsCandF motorshoulddrivetothefully open clockwise positionasviewedfromthepower end Remove jumper Remove the lead from terminal C or R motor should drive to the closed fully counterclock wise position M7161G and M7164G JumperterminalsCandF motorshoulddrivefullclosed fullycounterclockwise positionasviewedfromthe power end Remove jumper Remove the lead from termi nal C or R motor should...

Page 12: ...nd Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley Minnesota 55422 Scarborough Ontario M1P 2V9 Printed in U S A QUALITY IS KEY ...

Reviews: