Lyric Gateway Installation and Reference Guide
- 13 -
Wireless Zones
Wireless Zones
Wireless Zones
Wireless Zones (Continued)
RF
RF
RF
RF Transmitter Loop Numbers
Transmitter Loop Numbers
Transmitter Loop Numbers
Transmitter Loop Numbers
(Refer to this information when programming 5800 Series transmitters)
The following illustration shows the compatible transmitters, their associated input types and loop designations.
lyri
c-0
5
3
-V4
5 8 7 7
5 8 0 0 S S 1
E N R O L L A S
S U P E R V I S E D
5 8 7 8
ENROLL AS BUTTON
LOOP 1
(LOW SENSITIVITY)
LOOP 2
(HIGH SENSITIVITY)
5 8 9 8
E N R O L L A S
S U P E R V I S E D
SERIAL #1
LOOP 3
SERIAL #1
LOOP 4
SERIAL #2
LOOP 3
SERIAL #1
LOOP 2
SERIAL #1
LOOP 1
SERIAL #2
LOOP 2
3
AW
AY
ST
AY
1
2
4
OFF
ON
SiXFOB
LOOP 1
LOOP 2
LOOP 3
LOOP 5
LOOP 4
5 8 0 0 P I R - O D
E N R O L L A S
S U P E R V I S E D
5 8 0 0 P I R / 5 8 0 0 P I R - C O M
E N R O L L A S
S U P E R V I S E D
5 8 0 0 P I R - R E S
E N R O L L A S
S U P E R V I S E D
5 8 0 0 C O M B O
E N R O L L A S
S U P E R V I S E D
5 8 0 0 M i c r a
E N R O L L A S
S U P E R V I S E D
5 8 0 0 C O
E N R O L L A S
S U P E R V I S E D
LOOP 1
LOOP 1
(LOW
SENSITIVITY
LOOP 2
(HIGH
SENSITIVITY)
LOOP 3 (TEMP)
LOOP 4 (TAMPER)
SERIAL #1
LOOP 1
(HEAT/SMOKE)
LOOP 2
(MAINTENANCE)
LOOP 3
(LOW TEMP)
SERIAL #2
LOOP 1
(CO)
LOOP 2
(END OF LIFE)
LOOP
1
LOOP
1
LOOP
1
LOOP
1
LOOP 1
5806/5806W3/5807
5808/5808LST/5808W3
E N R O L L A S S U P E R V I S E D
LOOP 1
LOOP 1
5809
E N R O L L A S
S U P E R V I S E D
LOOP 1
5814
E N R O L L A S
S U P E R V I S E D
5804E
ENROLL AS
BUTTON
5 8 1 5 W G / 5 8 1 5 W G - B R
E N R O L L A S
S U P E R V I S E D
5 8 1 1
E N R O L L A S
S U P E R V I S E D
LOOP 4
LOOP 1
LOOP 2
LOOP 3
5 8 1 8 M N L
E N R O L L A S
S U P E R V I S E D
LOOP 1
LOOPS
1 - 3
LOOP 1
5 8 1 6 M N
E N R O L L A S
S U P E R V I S E D
LOOP 1
(TERMINALS)
LOOP 3
(TERMINALS)
ALTERNATE POSITION
FOR LOOP 2
LOOP 3
(TERMINALS)
5 8 2 1
E N R O L L A S
S U P E R V I S E D
5 8 2 0 L
E N R O L L A S
S U P E R V I S E D
5 8 1 9 S ( W H S & B R S )
E N R O L L A S
S U P E R V I S E D
LOOP 2
(REED)
5 8 1 9 S
E N R O L L A S
S U P E R V I S E D
5 8 1 9
E N R O L L A S
S U P E R V I S E D
LOOP 2
(REED)
LOOP 3
(TERMINALS)
LOOP 1
(TERMINALS)
5 8 1 6
E N R O L L A S
S U P E R V I S E D
LOOP 1
(TERMINALS)
LOOP 2
(REED)
LOOP 1
LOOP 1
5 8 2 2 T
E N R O L L A S
S U P E R V I S E D
LOOP 1
(HIGH
SECURITY)
LOOP 2
(STANDARD
SECURITY)
LOOP 3 (TILT MODE)
LOOP 4 (TAMPER)
5834-4
ENROLL AS BUTTON
5870API
E N R O L L A S
S U P E R V I S E D
5869
E N R O L L A S
S U P E R V I S E D
5 8 5 3
E N R O L L A S
S U P E R V I S E D
SERIAL #1
LOOP 4
SERIAL #2
LOOP 2
SERIAL #2
LOOP 3
SERIAL #1
LOOP 1
SERIAL #2
LOOP 4
SERIAL #2
LOOP 1
2
1
ON
LOOP 1
(TERMINALS)
LOOP 2
(REED)
LOOP 2
(REED)
LOOP 1
(INTERNAL
SHOCK
SENSOR)
NOTES
NOTES
NOTES
NOTES:::: (1) The 5806W3 smoke detector must be used in SIA applications.
(2) Button type devices send only fault and low battery signals; no restore or check-in signals.
Supervised RF devices send periodic check-in signals, faults, restore and low battery signals.
(3) The 5804E and 5834-4 encrypted (High-Security) devices must be activated while the system is
in Go/No-Go Test Mode. Refer to the transmitter’s Installation Instructions for complete details.
The system will confirm the enrollment of the encrypted device by beeping two times.
(4)
The 5800PIR-OD, 5800SS1, 5804E, 5814, 5821, 5877, and 5878 wireless transmitters have not been
evaluated by ETL.
Summary of Contents for Lyric LCP300-LC
Page 42: ...Lyric Gateway Installation and Reference Guide 42 Notes Notes Notes Notes ...
Page 43: ...Lyric Gateway Installation and Reference Guide 43 Notes Notes Notes Notes ...
Page 44: ...Lyric Gateway Installation and Reference Guide 44 Notes Notes Notes Notes ...
Page 45: ...Lyric Gateway Installation and Reference Guide 45 Notes Notes Notes Notes ...