background image

L7124U UNIVERSAL OIL ELECTRONIC AQUASTAT® CONTROLLER

69-1232—2

2

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow 
them could damage the product or cause a 
hazardous condition.

2.

Check the ratings given in the instructions and on 
the product to make sure the product is suitable for 
your application.

3.

The installer must be a trained, experienced 
service technician.

4.

After installation is complete, check out product 
operation as provided in these instructions.

WARNING

Electrical Shock Hazard.
Can cause serious injury or death.

Disconnect power supply before beginning 
installation to prevent electrical shock or 
equipment damage.

Mounting

The L7124U has a case that can be converted for either 
horizontal or vertical mounting. See Fig. 1.

IMPORTANT

Immersion well must fit sensing element and 
sensor bulb must rest against bottom of well.

New Installation

Order well assemblies for the L7124U separately; see 
form 68-0040, Wells and Fittings for Temperature 
Controllers. Boilers usually have tappings that allow 
the well to be mounted horizontally so boiler water of 
average temperature can circulate freely.

1.

Turn off all power and drain the boiler.

2.

If no tapping is provided, prepare properly sized 
and threaded tapping near the top of the boiler.

3.

Sparingly coat the well threads with pipe dope.

Fig. 1.  Case designed for vertical 

or horizontal mounting.

NOTE: Do not attempt to tighten by using the case as a 

handle.

4.

Install the well in the boiler tapping and tighten 
securely.

5.

Refill boiler and check for water leakage.

6.

Loosen but do not remove the clamp screw on the  
L7124U case.

7.

Insert the sensor element into the well until it 
bottoms. (If necessary, slightly bend the tube inside 
the case to hold the sensor against the bottom of 
the well.)

NOTE: Some models have an adjustable wire length to 

3 in. (76 mm). For these models, pull out extra 
wire length from inside the case, if needed.

8.

Fit the case into the well so the clamp on the case 
slides over the flange on the well.

9.

Securely tighten the clamp screw.

IMPORTANT

Best thermal response is obtained with a well 
that snugly fits the sensor. Insert the sensor 
until it rests against the bottom of the well. use 
a well of correct length and bend the wiring, if 
necessary, to hold the bulb against the bottom 
of the well.
If the well is not a snug fit on the sensor, use 
the heat-conductive compound (furnished with 
TRADELINE models) as follows: Fold the 
plastic bag of compound lengthwise and twist it 
gently. Then snip off end of bag and work the 
open end of the bag all the way into the well. 

Slowly pull out the bag while squeezing it firmly 
to distribute compound evenly in the well. Bend 
the wiring, if necessary, to hold the sensor 
against the bottom of the well and to hold outer 
end of the sensor in firm contact with the side of 
the well. See Fig. 2. Wipe excess compound 
from the outer end of the well.

Replacement Installation

Turn off all power and remove the old control. Refer 
to the cover insert of the old control to identify and tag 
each external lead as it is disconnected. If the old well is 
unsuitable for the new installation, remove it and proceed 
with instructions for new installation. If the old well is 
suitable, use it and an immersion well adapter (ordered 
separately) for the installation. (The well clamp may fit 
directly over the flange of the existing well spud and 
using the adapter may not be necessary.) The adapter 
has a flange at the wide end that fits into the well clamp 
and is slotted lengthwise to accommodate the sensor 
wire.

1.

Loosen but do not remove the well clamp screw on 
the side of the control case. 

2.

Pull out the wire until the sensor bottoms in the 
well. Place adapter, if used, around the sensor wire 
so it fits into the slot. See Fig. 2.

3.

Make sure the wide end of the adapter fits into the 
hole in the case. Position immersion well clamp 
snugly over the flange of the adapter and tighten 
the clamp screw.

4.

Insert the sensor into the well as shown in Fig. 2. 
(Distribute the heat-conductive compound in the 
tube prior to bulb insertion.)

5.

Securely tighten the setscrew against the adapter.

BRACKET POSITION FOR 
VERTICAL MOUNTING

BRACKET POSITION FOR 
HORIZONTAL MOUNTING

M8890

Summary of Contents for L7124U

Page 1: ... mechanical distance Some models also have a Low Limit and Low Limit Differential adjustment The range of the Low Limit dial is from 110 F to 220 F 43 C to 104 C Rotating the Low Limit potentiometer fully counterclockwise disables the low limit function and turns on the Low Limit Disabled LED The L7124U is designed for use with 24 Vac electronic and electromechanical thermostats and has screw type...

Page 2: ...e flange on the well 9 Securely tighten the clamp screw IMPORTANT Best thermal response is obtained with a well that snugly fits the sensor Insert the sensor until it rests against the bottom of the well use a well of correct length and bend the wiring if necessary to hold the bulb against the bottom of the well If the well is not a snug fit on the sensor use the heat conductive compound furnished...

Page 3: ...proved for use with copper wire only Follow the appropriate wiring diagrams shown on the inside of the front cover of the L7124U or in Fig 3 and 4 Fig 3 L7124U single zone connections SENSOR WIRES IMMERSION WELL CLAMP SCREW IMMERSION WELL CLAMP M16120 HEAT CONDUCTIVE COMPOUND OPTIONAL CONTROLLER CASE BOILER IMMERSION WELL SENSOR LOW LIMIT HIGH LIMIT DIFF SENSOR PWR T L2 T TSTAT DSBL LL B B2 B1 C2 ...

Page 4: ...CULATOR TO ADDITIONAL R845A RELAYS FOR OTHER ZONES LOW LIMIT HIGH LIMIT DIFF SENSOR PWR T L2 T TSTAT DSBL LL B B2 B1 C2 ZR ZC C1 C ZC 1 2 M17777 1 1 2 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED CONTROL CASE MUST BE CONNECTED TO EARTH GROUND USE GROUNDING SCREW PROVIDED LINE VOLTAGE OIL BURNER RELAY LINE VOLTAGE CIRCULATOR LOW VOLTAGE THERMOSTAT T1 LEGEND LED SENSOR...

Page 5: ...he fixed differential 3 Low Limit Boiler temperature has gone below the low limit setting minus the low limit differential and has not gone above the low limit setting 4 Error The controller has detected an error condition e g open sensor and has shut down the burner output The circulator and ZC output are energized The controller continues to function and automatically restarts if the error condi...

Page 6: ...System Condition Check Corrective Action Boiler is cold house is cold PWR LED Off Check 120 Vac system power 1A fuse on L7124U PWR LED On TSTAT LED Off Check Thermostat Thermostat wiring PWR LED On TSTAT LED On B burner LED On Check 120 Vac B1 B2 If no replace burner relay If yes check burner and wiring PWR LED On TSTAT LED On LL DSBL LED Flashing Refer to LED diagnostics Table 3 Boiler is hot hou...

Page 7: ...7 69 1232 2 ...

Page 8: ... on recycled paper containing at least 10 post consumer paper fibers Home and Building Control Home and Building Control Honeywell Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 ...

Reviews: