- 4 -
2.2 Installation Suggestions
Here, items to be cautioned at the time of installation of IPC500 (temperature
controller) to panel are explained. Protection from the environment and
convenience of operation needs to be considered.
1) Allow sufficient distance for ventilation.
2) Do not install it right above of equipment (transformer, large capacity resistor, etc.) that
generates a lot of heat in the panel.
3) Install it as far as possible from high voltage equipment and power-driven machinery or
wiring. Otherwise, install it in a different panel.
4) To reduce and prevent noise, please use special purpose grounding. If wiring to the point
of grounding is far, please use heavy insulation wire as a special purpose grounding
cable and ground it through a conduit tube.
5) For IPC500’s communication cable and data lines, do not tie it up together with those
that cause noise such as the power supply wiring of a power-driven machine. In case it is
wired to the same duct, connect shield wire to FG terminal of the main frame.
6) When installing panel, use a flat panel that is not curved.
7) To prevent product damage, fasten screws just once when bracket does not move back
and forth.
8) The Cooling method of IPC500 is based on vertical installation which needs natural air
cooling. In case it is installed horizontally or on a slant, range of operating temperature is
somewhat limited.
9) If you want to use it after keeping it under 0
°
C, you need to warm it up for two
hours at room temperature before plugging it in. Otherwise, it may not function
normally and the product may be damaged.
2.3 Panel Cut Dimensions
199.5
119
<Figure 2.3.1>
Unit: mm