- 20 -
Sequence of Operation
1. Setting up temperature(TEMP)/PV/ABS/HIGH, Absolute value (ABS VALUE),
Operation Differential (OPER DIFF), and DELAY(SEC)
— Press PV at object value selection key (3). The PV key is reversed.
— Press ABS at operating point selection key (4). The ABS key is reversed.
— Press HIGH at output operation selection key (5). The HIGH key is reversed.
— Enter absolute value after pressing ABS VALUE setup key (6). Input of ABS
VALUE is allowed only within SET RANGE on the right-hand side.
(Set range : -100 ~ 300
°
C)
— Enter operation differential after pressing OPER DIFF setup key (7). Input of
OPER VALUE is allowed only within SET RANGE on the right-hand side.
(Set range : 0 ~
±
9.9
°
C)
— Enter delay time after pressing DELAY time setup key (8). Input of DELAY time
is allowed only within SET RANGE on the right-hand side.
(Set range : 0 ~ 99 SEC)
2. Setting up TEMP/PV/DEV/HIGH, deviation value (DEV VALUE), OPER DIFF, and
DELAY(SEC)
— Press TEMP at object selection key (2). The TEMP key is reversed.
— Press PV at object value selection key (3). The PV key is reversed.
— Press DEV at operating point selection key (4). The DEV key is reversed.
— Enter HIGH at output operation selection key (5). The HIGH key is reversed.
— Enter deviation value after pressing DEV VALUE setup key (6). Input of
deviation value is allowed only within SET RANGE on the right-hand side.
( Set range: -99.9 ~ 99.9
°
C)
— Enter operation difference after pressing OPER DIFF setup key (7). Input of
operation differential is allowed only within SET RANGE on the right-hand side.
(Set range : 0 ~
±
9.9
°
C)
— Enter delay time after pressing DELAY time setup key (8). Input of delay time
input is allowed only within SET RANGE on the right-hand side. (0 ~ 99 SEC)
3. Setting up TEMP/SP/ABS/ON, minimum value (MIN VALUE), maximum value(MAX
VALUE), and DELAY(SEC)
— Press TEMP at object selection key (2). The TEMP key is reversed.
— Press SP at object value selection key (3). The SP key is reversed.
— If you choose SP, the ABS key is automatically selected.
— Press ON at output operation selection key (5). The ON key is reversed.
— Enter minimum value after pressing MIN VALUE setup key (6). Input of MIN
VALUE is allowed only within SET RANGE on the right-hand side.
(Set range : -100 ~ 300
°
C)