- 34 -
Item
Specifications
PID ZONE Setup
Up to six zones are classified for the field of temperature and input of
PID constant can be setup in each field (While program is being
executed, PID constant of the field is used automatically, if SP exists in
the field).
Note 1) 6 temperature fields
RUN Output
Open collector output ON/OFF X 1
"ON" when program is RUN; "OFF" when program is END
END Output
Open collector output ON/OFF X 1
"ON" when program is END; "OFF" when program is ON
TIME SIGNAL
Open collector output ON/OFF X 4
It is possible to set up to 10 ON/OFF times
Others
In the program mode, control operation starts for program start
(Control output of the total of the previous is OFF)
For those other than transmitted output (Power failure, Alarm, stop),
output of the total is OFF when the program stops.
4.5 Control output specifications (INNER Signal)
Item Specifications
Output points
Open collector output ON/OFF X 6
(MAX DC30V MAX 50mA / 1ch internal resistance 47
Ω
)
Object Temperature(TEMP)
Object value
Set Point (SP) / Present value (PV) / Target value (DV)
Operating point Absolute value (ABS) / Deviation (DEV)
Output
operation
ZONE ON/OFF / Operation direction (LOW/HIGH)
Temperature
Absolute value
-100.0 ~ 300.0
°
C
Deviation value
-99.9 ~ +99.9
°
C
Operation
range
Action differential
±
0.0 ~
±
9.9
°
C
Setup item
ON delay time 0 ~ 99 seconds