7. C300 Controller Operation
7.4. Control Builder block icon descriptions
Icon
Represents . . .
C300 Controller
(C300STATE)
(green,
simulation)
C300 is non-redundant. Simulation mode
enabled.
Run or OK
(green & white)
Primary C300 is synchronized.
Run or OK
(green & white,
pause)
Primary C300, standby synchronization.
Run or OK
(green & yellow)
Primary C300 is not synchronized and partner
C300 is visible.
Run or OK
(green &
shadow)
Primary C300 is not synchronized and partner
C300 is absent or incompatible.
Run or OK
(white & green)
Secondary C300 is synchronized.
Backup
(white & green,
pause)
Secondary C300, standby synchronization.
Backup
(yellow & yellow)
Secondary C300 is not synchronized and
partner C300 is visible.
Backup
(shadow &
yellow)
Secondary C300 is not synchronized and
partner C300 is absent or incompatible.
Backup
(blue)
C300 is non-redundant.
Idle Soft Fail
(blue,
simulation)
C300 is non-redundant. Simulation mode
enabled.
Idle Soft Fail
(blue & white)
Primary C300 is synchronized.
Idle Soft Fail
(blue & white,
pause)
Primary C300, standby synchronization.
Idle Soft Fail
(blue & yellow)
Primary C300 is not synchronized and partner
C300 is visible.
Idle Soft Fail