Series 8 C300 Controller User's Guide
Honeywell
171
6. Load C300 Controller Configuration
6.5. Reloading components from project
Block to be
Re-Loaded
Conditions or Restrictions
The CM is ACTIVE.
IOLINK
The C300 Block must be present and previously loaded.
The state of previously loaded IOMs must be IDLE.
IOLINK block configuration parameters are re-loaded along with
configuration data for previously loaded IOM Blocks.
Re-load fails and is cancelled if the C300 is not loaded, or the
state of at least one previously loaded IOM is in RUN.
CEE
The C300 Block must be present and previously loaded.
The state of the CEE must be IDLE.
C300 with
Contents
The following blocks are re-loaded unless they are de-selected in
the Load dialog box.
C300 Block
IOLINK Block with Contents for IOLINK 1
IOLINK Block with Contents for IOLINK 2
CEE Block with Contents
NOTE
:
The configuration data of any previously loaded IOMs and CMs is not reloaded. You
must reload any desired IOMs and CMs.