194
Series 8 C300 Controller User's Guide
Honeywell
R500
April 2017
7. C300 Controller Operation
7.7. Initiating Synchronization command
7.7
Initiating Synchronization command
To initiate a synchronization command manually to a redundant C300 Controller pair,
perform the following steps.
Prerequisites
You can view active redundant C300 Controller pair on the
Monitoring
tab in Control
Builder.
Commanding synchronization
Step
Action
1
In the
Monitoring
tab, double-click the primary
C300
icon to The
Parameters
configuration form appears.
2
Click the
Redundancy
tab.
3
Click
Enable Synchronization
.
4
Click
Yes
to confirm the action and issue the synchronize command.
5
Confirm that the
Auto Synchronization State
becomes
ENABLED
and
confirm that
sync
cycles in the primary C300 Controller's 4-character display.
6
Click
OK
to close the
Parameters
form.
7
This completes the procedure.