5. C300 Configuration Form Reference
5.4. IOLINK Block
R500
April 2017
Series 8 C300 Controller User's Guide
Honeywell
155
IOTA Summary tabs
The IOTA Summary tab contains additional statistics for Series 8 IOMs residing on the
IOLINK, which is used for maintenance and performance monitoring of the IOLINK
interface. The following table summarizes the parameter data you can monitor and/or
configure on the
IOTA Summary
tab of the configuration form for the selected IOLINK
block.
Plain Text
Parameter Name
User
Configurable
Notes
IOTA
Physical Address
PHYSADDRSC(1…4)
No
Indicates the physical
address for the Series 8
IOM.
Actual Module Type
PHYSMODTYPESC1
No
Indicates the physical
Series 8 IOM type.
IOM Status
PHYSIOPSTSSC1
No
Shows the status of the
specific physical Series
8 IOM.
IOM Commands
PHYSCOMMANDSC1
No
Shows Series 8 IOM
Commands.
Firmware Revision
FNWREVSC1
No
Indicates the Series 8
IOM Firmware revision.
Boot FW Revision
BOOTREVSC1
No
Indicates the Series 8
IOM Boot Code
revision.
Hardware Revision
HDWREVSC1
No
Indicates the Series 8
IOM Hardware
Revision.
Active Receive
Channel
PHYRCVCHNSC1
No
Indicates the actual
active receive channel
for the Series 8 IOM.
Channel A Errors
PHYCHNERRASC1
No
Shows the I/O Link
errors on Channel A for
the Series 8 IOM.