Normally Closed
Normally Closed will force the relay output to be closed when the
output is not active.
NOTE: For DCV Inlets/Outlets and Internal additive pulse output, GP output
condition is fixed to Normally Open.
4.6 Configure Deadman (25)
Use the Configure Deadman sub-menu of the System menu to set the
Deadman System time-outs.
Deadman Timer
If enabled, the operator must repeatedly (within the settable timeout
period) press a key on the keypad of the instrument to prevent the
Deadman system being triggered.
Constraints:
Any key apart from STOP
Select one of the following options:
Enable
Disable*
Deadman Warning
Timeout
Sets the time after the activation of the Deadman warning indicator
within which an instrument key must be pressed to prevent the load
being paused.
If the timeout expires the Deadman Indicator (GP Output) is activated.
Constraints:
Only if Deadman enabled
It is common practice to have a visual indicator activated by this output
contact.
Enter a value in the following range:
10 to 999 seconds (150*)
Deadman Pause
Timeout
If the timeout expires the Deadman Bell (GP Output) is activated and
loading is paused.
An audible alarm (bell or siren) may be activated by this output contact.
Constraints:
Only if Deadman is enabled.
Enter a value in the following range:
10 to 999 seconds (30*)
Deadman Terminate
Timeout
Sets the time after the activation of the load pause sequence during
which an instrument key must be pressed to prevent a load being
terminated. If the load is terminated by activation of the Deadman
system the Deadman Callout (GP Output) relay is activated.
The Deadman Callout output may be used to interlock with the bay or
site emergency shutdown system.