3. Configuration
3.5. Control Set Up Group
26
EDC201 / EDC202 / EDC203 Product Manual
Revision 2.0
July 2015
Set up
Group
Function
Prompt
7-Segment
Code
Default
Value
Selection
or Range
of Setting
7-Segment
Code
Parameter
Definition
Top Display
Upper Display
Lower Display
REVERSE
Reverse
REVR
REVERSE ACTING
CONTROL: Based
on the PID control,
the controller’s
output decreases as
the process variable
increases.
Direct
DIRT
DIRECT ACTING
CONTROL—Based
on the PID control,
the controller’s
output increases as
the process variable
increases.
RLYSTATE
RLST
OFF
OFF
OFF
It is used for
controlling the digital
output. Digital output
de-energizes when
the control output is
0%.
ON
ON
It is used for
controlling digital
output. Digital output
energizes when
control output is 0%.
Minimun On
Time
MIOT
3
1 ~ 6
Keeps the high level
enabled for set time
each time the output
is enabled.
ATTENTION Only
applicable for
ON/OFF control.