3. Configuration
3.5. Control Set Up Group
24
EDC201 / EDC202 / EDC203 Product Manual
Revision 2.0
July 2015
Set up
Group
Function
Prompt
7-Segment
Code
Default
Value
Selection
or Range
of Setting
7-Segment
Code
Parameter
Definition
Top Display
Upper Display
Lower Display
Time B
TImB
Proportional Output
based on PID B has
a resolution of 3.33
msec. Cycle Time is
adjustable from 1 to
120 seconds.
Unlike the PID A
equation, the
controller gives only
an integral response
to a setpoint change,
with no effect on the
output due to the
gain or rate action,
and it gives full
response to PV
changes. Otherwise
controller action is
as described for the
PID A equation.