3. Configuration
3.4. Input Set Up Group
Revision 2.0
EDC201 / EDC202 / EDC203 Product Manual
21
July 2015
Set up
Group
Function
Prompt
7-Segment
Code
Default
Value
Selection or
Range of
Setting
7-Segment
Code
Parameter
Definition
Top Display
Upper Display
Lower Display
Rlow
ANL
0 -999
~
9999
0
Input low range
value. Input high
range of TC and
RTD input types are
generated by
searching the
corresponding table
automatically
depending on the
input type. It cannot
be modified.
RATIO
RATO
1
-20.00 ~
20.00
Ratio on input.
BIAS
BIAS
0 -999
~
9999
Bias is used to
compensate the
input for drift of an
input value due to
deterioration of a
sensor, or some
other cause. Select
the Bias value you
want on the Input.
FILTER
FILT
0
0 ~ 120s
A software digital
filter is provided for
the Input to smooth
the input signal. 0
means filtering
prohibited.
BURNOUT
BRN
FS FS
FS
Pre-configured
Failsafe output
(selected in the
CONTROL Set up
Group) applied if a
failed input is
detected (does not
apply for an input out
of range).