![Honeywell EDC 200 Series Product Manual Download Page 37](http://html.mh-extra.com/html/honeywell/edc-200-series/edc-200-series_product-manual_149930037.webp)
3. Configuration
3.5. Control Set Up Group
Revision 2.0
EDC201 / EDC202 / EDC203 Product Manual
25
July 2015
Set up
Group
Function
Prompt
7-Segment
Code
Default
Value
Selection
or Range
of Setting
7-Segment
Code
Parameter
Definition
Top Display
Upper Display
Lower Display
TPSC
TPSC
The Three Position
Step Control
algorithm allows the
control of a valve (or
other actuator) with
an electric motor
driven by two
controller relay
outputs.
The Three Position
Step Control
algorithm provides
an output display
(OUT) which is an
estimated motor
position, since the
motor is not using
any slidewire
feedback. Although
this output indication
is only an
approximation, it is
“corrected” each
time the controller
drives the motor to
one of its stops (0 %
or 100 %).
CYC Time
CYCT
1 1~
120
Cycle time used for
time proportioning
control. If the control
output type is RLY,
Units: s; if the control
out type is SSR
driver, Units: 1/3s
ACTION
ACTN
CONTROL OUTPUT
DIRECTION: Select
direct or reverse
output action.