5-4
NOTE
•Select the program pattern setting system using setup data setting
C61
.
0: combined use of RAMP-X and RAMP-T
1: combined use of RAMP-X and RAMP-E
•Select time setting units using setup data setting
C62
.
0: hours and minutes
1: minutes and seconds
2: 0.1 seconds
•Select
θ
setting units using setup data setting
C62
.
0: SPU/hour
1: SPU/min
2: SPU/sec
•Select SP setting and SP setting decimal position using setup data setting
C65
.
0: XXXXX
1: XXXX.X
2: XXX.XX
3: XX.XXX
4: X.XXXX
•External switch for pulse input requires 1: RAMP-E using a setup data setting
between
C71
to
C74
.
•The pulse input interval time can be checked by setting event type 93 in the event.
Event type 93 is RAMP-E time monitored during a period of 0.0 to 3000.0
seconds.
Even when a setting is exceeded and there is no pulse input, the event remains on.
Chapter 5. FUNCTIONS