7-29
0 to 127
[Description:]
Ò----Ó is displayed for model without communications and
when
C97
is set to a value that is not equal to 0 and
setting cannot be performed.
When
C76
is set to 0, the communication function is not
activated.
0
C 76
76
Communication address
0: 9600bps
1: 4800bps
2: 2400bps
3: 1200bps
[Description:]
Ò----Ó is displayed for model without communications and
when
C97
is set to a value that is not equal to 0 and
setting cannot be performed.
0
C 77
77
Transmission rate
0: 8 bits, even parity, 1 stop bit
1: 8 bits, no parity, 2 stop bits
[Description:]
Ò----Ó is displayed for model without communications and
when
C97
is set to a value that is not equal to 0 and
setting cannot be performed.
0
C 78
78
Transmission code
0: CPL
1: ST221 (no PV trend)
2: ST221 (PV trend)
[Description:]
Ò----Ó is displayed for model without communications and
when
C97
is set to a value that is not equal to 0 and
setting cannot be performed.
0
C 79
79
Communication
0 : RS-485
1 : RS-232C
[Description:]
Ò----Ó is displayed for model without communications and
when
C97
is set to a value that is not equal to 0 and
setting cannot be performed.
0
C 80
80
Communication method
[Description:]
Can only be referenced for mechanical service use.
Ð
C 81
81
ROM ID
Ð
C 82
82
ROM ITEM
Ð
C 83
83
ROM revision
Ð
C 85
85
CPU board ID
Ð
C 86
86
I/O board ID
[Description:]
Ò-----Ó is displayed and setting cannot be performed.
----
C 87
87
Unused
----
C 88
88
Unused
----
C 89
89
Unused
1
C 90
90
PID type
0: Yes
1: No
0
C 91
91
PV1 burnout
0: Yes
1: No
0
C 92
92
PV2 burn out
0: Does not go on a second time off in time proportional cycle.
1: Goes on a second time in time proportional cycle.
0
C 93
93
Time proportional output
0: Does not go on a second time off in time proportional cycle
1: Goes on a second time in time proportional cycle
0
C 94
94
Time proportional output
Ð
C 84
84
Data version
Item code
Item
No.
User
settings
Settings and descriptions
Factory default
settings
2 to 22mA
2 to 22mA
15
C 95
95
Voltage output control (CH1)
15
C 96
96
Voltage output control (CH2)
0 to 15
The backplate terminal is used when set to 0.
The loader jack is used for settings 1 to 15.
[Description:]
When set to 0, communications cannot be performed on
model without communications.
When set to 0, communications conditions are selected
using
C76
to
C80
.
The communication address is used for settings 1 to 15.
4800bps, 8 bits, even parity, 1 stop bit
0
C 97
97
Communications port
0 to 255
[Description:]
A setting of 0 is normally used.
0
C 98
98
Special function
0: Improved
1: Compatible with MarkI
Chapter 7. PARAMETER SETUP
Summary of Contents for DCP552 Mark II
Page 1: ...EN1I 6187 Issue 5 12 01 DCP552 Mark ΙΙ Digital Control Programmer User s Manual ...
Page 20: ...2 5 Chapter 2 NAMES AND FUNCTIONS OF PARTS 0 1 ...
Page 116: ...7 17 0 1 2 32 32 3 4 5 6 7 8 8 9 Chapter 7 PARAMETER SETUP ...
Page 208: ...12 18 Figure 12 11 Current Outputs Chapter 12 CALIBRATION ...
Page 229: ......
Page 230: ......
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ......
Page 235: ......
Page 236: ......
Page 237: ......
Page 238: ......
Page 239: ......
Page 240: ......
Page 247: ...No CP UM 5025E ...