LION System
Planning
11
EN1Z-0921GE51
R0315
XW885 Cable Details
1
8
RJ45 plug with clip at front
and protective sheathing
RS232 plug
sub-D female
1
5
4
3
2
9
8
7
6
SHIELD
XW885
RxD
DCD
RTS
+5V
TxD
CTS
4
5
DTR
RI
GND
3
6
2
7
Fig. 7
CLLIONLC01/laptop cable details
XW582 Cable Details
to XC5010C
1
5
4
3
2
9
8
7
6
XW582
SHIELD
RxD
GND
+5VE
TxD
YELLOW
BROWN
GREEN
WHITE
1
4
3
2
CLMMI00N22
WIRING
TERMINALS
LOOSE
ENDS
Fig. 8
XW582 cable details
XW585 Cable Details
1
5
4
3
2
9
8
7
6
1
5
4
3
2
9
8
7
6
XW585
SHIELD
+5V
RxD
GND
RTS
TxD
RS232 plug
sub-D female
RS232 plug
sub-D female
Fig. 9
XW585 cable details
XW586 Cable Details
1
5
4
3
2
9
8
7
6
1
2
3
6
7
8
4
5
RS232 plug
sub-D male
DCD
DSR
RxD
RTS
TxD
CTS
DTR
GND
XW586
RJ45 plug with clip at front
+5V
Fig. 10
XW586 cable details
L
ON
W
ORKS
Bus Termination Modules
Type
Description
XAL-Term2
L
ON
W
ORKS
connection and ter-
mination module, which can be
mounted on DIN rails and in fuse
boxes
Table 15 L
ON
W
ORKS
Bus termination modules
Cable Specifications
Power Supply Cables
When checking the length of the power supply cable, the
connection cables to all I/O modules must be taken into
account.
Max. length
3 m (per side of the controller),
see Fig. 32 on page 24
Cross section
min. 0.75 mm
2
(AWG 18)
Table 16 Power supply cables specification
Panel Bus Cables
Max. length
40 m
Cable type
twisted pair, e.g., J-Y-Y 2 x 2 x 0.8
Table 17 Panel Bus cables specification