LION System
Wiring
and Setting Up the System
27
EN1Z-0921GE51
R0315
Setting Address of Panel Bus I/O Modules
During engineering, each Panel Bus I/O module is assigned
its own unique address. For the sake of clarity for
maintenance personnel, it is recommended that you
address the Panel Bus I/O modules in ascending order
0 through F.
Hex switch
0 1 2 3 4 5 6 7
Address
01 02 03 04 05 06 07 08
Hex switch
8 9 A B C D E F
Address
09 10 11 12 13 14 15 16
Table 24 HEX switch settings and addresses
►
Use the rotary HEX switch to set the address to the one
already defined using the engineering tool.
LOCK
4
4
Fig. 37
HEX switch location
NOTE:
If the HEX switch is changed, the Panel Bus I/O
module will revert to its default configuration.
NOTE:
With
L
ON
W
ORKS
Bus I/O modules, the HEX
switch is without function.
Setting I/O Bus Switch
►
Set the I/O Bus switch S2 of the CLLIONLC01 depending
on the modules connected to terminals 71 … 78 and the
desired communication as follows:
Communication S2 setting
Terminals
L
ON
W
ORKS
Bus
only
LON
71 … 74 L
ON
W
ORKS
Bus
75 … 78
L
ON
W
ORKS
Bus
11 … 14
L
ON
W
ORKS
Bus
Panel Bus and
L
ON
W
ORKS
Bus
Panel
71 … 74 Panel Bus
75 … 78 Panel Bus
11 … 14 L
ON
W
ORKS
Bus
Table 25 I/O Bus switch settings
Panel
LO N
S2
I/O Bus
Fig. 38
S2 I/O Bus switch