LION System
Wiring
and Setting Up the System
23
EN1Z-0921GE51
R0315
Connecting Power Supply
The LION System can be powered by one or more external
transformers.
NOTE:
The max. length for the power supply cable from
a transformer is 3 m. This also includes the
length of the modules and the connection cables
between the rails.
NOTE:
Referring to Fig. 30, the following conditions must
be fulfilled: A
≤
3 m and B
≤
3 m
Single or the First Transformer
►
Connect the transformer to terminals 1 and 2 of the
CLLIONLC01 Controller.
I/O
I/O
I/O
CPU
2
1
B
A
A 3 m
AND
B 3 m
Fig. 30
Wiring power supply from the (first) transformer to
the controller module
Additional Transformer
►
Connect the additional transformer in a second room or
cabinet to terminals 73 and 74 or 77 and 78 of an
I/O module.
I/O
I/O
71
72
73
74
MAX. 3 m
TRANS-
FORMER 2
Fig. 31
Wiring the power supply from a second
transformer
NOTICE
Equipment damage!
►
Do not use bridge connectors to connect modules
powered by different transformers.
►
When connecting modules powered by different
transformers using cables, be sure to not connect
terminals 73 and 77.