Section 3 - Installing the Control
3-19
Keyswitch Tamper Operation
The tamper switch need not be used for fire or UL
Household Burglary installations. For UL Commercial
Burglary installations, the tamper switch must be
wired to a zone (zone 6 in
Figure 3-23
).
Program that zone for Day Trouble/Night Alarm
(response type 5). When the keyswitch is removed from
the wall, the tamper switch opens, causing an alarm or
trouble on the zone. This also causes the control to
disable keyswitch operation until the tamper is restored
and the associated partition is disarmed.
Wiring for the Remote Keyswitch
To install the 4146 keyswitch, perform the following
steps:
Step Action
1
Connect the 4146 to the panel as shown in
Figure 3-23
.
2
If you are using the tamper, make sure it is
connected to a zone.
2K ELOR
2K ELOR
TAMPER SWITCH
(CONTACTS CLOSE WHEN
SWITCH DEPRESSED).
LOCK SWITCH
(NORMALLY OPEN)
+
TO J7 / OUT 2
TO J7 / OUT 4
TO AUX POWER
(TERMINAL 6)
ZONE
ZONE
TO ZONE 7 (+)
(TERMINAL 20)
YELLOW
WHITE
GREEN
(READY)
RED
(ARMED)
RED
BLACK
820
ohms
820
ohms
J7_keyswitch
Figure 3-23: Remote Keyswitch Wiring
Remote Keypad Sounder
An optional Amseco PAL 328N Piezo Sounder can be
used to duplicate the sounds produced by the keypad’s
built-in sounder. The panel will remote all sounds (e.g.,
alarm, trouble, chime, entry/exit, etc.) produced by the
keypad’s built-in sounder except for the short beeps
associated with keypad key depression. One application
of this feature might be to produce chime sounds at a
distant location from the panel’s keypads.
Remote Keypad Sounder Setup
To setup for a remote keypad sounder, connect the piezo
sounder to the panel’s positive auxiliary power output
and to Output 1 on the J7 connector as shown in
Figure
3-24
.
Program field 1
✳
46 Auxiliary Output Enable with a [
2
].
1 2
3
4
5
6
7
8
9
GRAY (GROUND)
YELLOW (OUT 1)
WHITE (GROUND)
RED (OUT 2)
GREEN (GROUND)
BROWN (OUT 3)
BLUE (GROUND)
BLACK (OUT 4)
J7 CONNECTOR
IF USED.
1. OUT 1 IS NO LONGER
USABLE FOR SMOKE
DETECTOR RESET
OR GROUND START
(SEE FIELD 1*46).
2. OUT 2, 3, 4 CAN STILL BE
USED TO PROVIDE ALARM
STATUS INDICATIONS OR
TO OPERATE A KEYSWITCH
(SEE FIELD *15).
N/U
4142TR CABLE
BLACK
–
AMSECO PAL-328N
PIEZO SOUNDER
+
RED
TO AUX POWER +
TERMINAL 6
10mA CURRENT DRAIN)
J7_trigcon-001-V0
Figure 3-24: Remote Keypad Sounder Wiring
WWW.DIYALARMFORUM.COM
Summary of Contents for Ademco VISTA-50P
Page 2: ...ii WWW DIYALARMFORUM COM ...
Page 12: ...VISTA 50P VISTA 50PUL Installation and Setup Guide 2 4 WWW DIYALARMFORUM COM ...
Page 40: ...VISTA 50P VISTA 50PUL Installation and Setup Guide 3 28 WWW DIYALARMFORUM COM ...
Page 48: ...VISTA 50P VISTA 50PUL Installation and Setup Guide 4 8 WWW DIYALARMFORUM COM ...
Page 64: ...VISTA 50P VISTA 50PUL Installation and Setup Guide 5 16 WWW DIYALARMFORUM COM ...
Page 78: ...VISTA 50P VISTA 50PUL Installation and Setup Guide 6 14 WWW DIYALARMFORUM COM ...
Page 82: ...VISTA 50P VISTA 50PUL Installation and Setup Guide 7 4 WWW DIYALARMFORUM COM ...
Page 84: ...VISTA 50P VISTA 50PUL Installation and Setup Guide 8 2 WWW DIYALARMFORUM COM ...
Page 98: ...VISTA 50P VISTA 50PUL Installation and Setup Guide B 2 WWW DIYALARMFORUM COM ...
Page 100: ...VISTA 50P VISTA 50PUL Installation and Setup Guide C 2 WWW DIYALARMFORUM COM ...
Page 102: ...VISTA 50P VISTA 50PUL Installation and Setup Guide D 2 WWW DIYALARMFORUM COM ...
Page 110: ...WWW DIYALARMFORUM COM ...
Page 111: ...WWW DIYALARMFORUM COM ...