System Programming
Tests Menu
Simulation Mode
This mode deactivates network communication Information Updates. It
can be combined with any of the three previous modes (example: using
the Simulation mode when in Debug mode allows the user to test the
entire system [groups, events, etc] without triggering any actions or
using any additional material such as gases). It allows you to simulate
gas concentrations over an associated scale for each transmitter,
sequentially:
Alarm levels A, B and C are evaluated according to the simulated gas
concentration and events are evaluated and actions are taken.
While in simulation mode, the controller is unaware of the device’s
actual network status. This mode can be stopped at any time in the
Test menu (see Normal System Operation).
If one of these modes has been activated, the system will automatically
return to Normal Mode after 12 hours of inactivity. (No changes will be
lost.)