510324
301C User Manual
19
4/07
Honeywell
Introduction
Relay Output
Relay Output
The relay output can withstand up to 5A at 30Vdc or 250Vac (resistive
load only). Relays can be used to activate horns and strobes. Although
each relay is programmed with a default setting (below), they can be
configured using the controller programming menu.
If relays are set to Normally closed, the relay is powered up with the
controller and the device linked to the relay is functioning. The relay will
shut down when the specified alarm condition is reached.
If the relay is set to normally open, the relay will remain off when the
controller is powered up and the device connected to the relay will only
be activated when the specified alarm condition is reached.
Note: These functions are reversed if the controller Failsafe mode has
been activated.
RELAY OUTPUTS
N.O.
N.C.
COMM
Normally closed
Normally open
Summary of Contents for 301C
Page 1: ...Centrale Controller Manuel de l utilisateur 301C User Manual ERP 510324 4 07 ...
Page 2: ......
Page 3: ...Controller Unit 301C User Manual ERP 510324 4 07 ...
Page 4: ......
Page 6: ......
Page 8: ......
Page 10: ......
Page 14: ......
Page 108: ......
Page 110: ......
Page 114: ......
Page 115: ...Centrale 301C Manuel de l utilisateur ERP 510324 4 07 ...
Page 116: ......
Page 118: ......
Page 120: ......
Page 122: ......
Page 126: ......
Page 210: ......
Page 220: ......
Page 226: ......
Page 228: ......
Page 232: ......