Galaxy 3 Series Installation Manual
A-3
Configuring a MAX Reader into the System
MAX readers can only be configured into the Galaxy system from engineer mode.
NOTE:
When adding a MAX reader to a Galaxy panel ensure that there are no more than eight MAX
readers connected to the RS485 (
AB
) line.
Wire the MAX as per the instructions given with figure 5-1 then access engineer mode.
The MAX reader must be assigned as either an
On-Line
or a
Stand-Alone
module using option
63.2.2
= OPTIONS.MAX.MAX Address:
0 =
On-Line:
The MAX is fully integrated with the Galaxy system and communicates via the AB
line, sharing system resources and facilities.
1 =
Standalone:
The MAX operates as an entirely independent unit. The Galaxy does not monitor
the MAX for alarms, tampers or power failure.
NOTE:
Early versions of MAX readers cannot convert between the stand-alone and on-line operating
modes:
•
MX01S (software V1.23)
is a dedicated stand-alone reader. This cannot be converted to
on-line mode and must not be connected to the Galaxy AB line. The horn output is fully
functional.
•
MX01 (software V1.23)
is programmed as an on-line reader. The horn output is non-
functioning. The reader can be reprogrammed, via the Galaxy system, into stand-alone
mode, however, once programmed as stand-alone it cannot be converted to on-line mode.
In stand-alone mode the horn output is fully functional.
•
MX01 (software V1.32)
can be reprogrammed as stand-alone or on-line as often as
required. In on-line mode, the horn output is non-functioning; in stand-alone mode the horn
output is fully functional.
Configuring as a Stand-Alone MAX
1.
Ensure that the MAX is connected to the Galaxy (
RS485 AB line
) and the MAX mode is enabled
(option
63.2.1 = OPTIONS.MAX.MAX Mode
).
2.
Select option
63.2.2 = OPTIONS.MAX.MAX Address
and press the
ent
key; the Galaxy
searches for the MAX with the highest address (the new MAX reader). The Galaxy 500 and 512
prompt for the AB line (1 – 4) that is to be searched; select the line and press the
ent
key. On
locating the MAX address, the keypad prompts for the
OPERATING MODE
of MAX to be assigned:
select
1 = Standalone
and press the
ent
key. The MAX reader is readdressed as
32
.
When the reprogramming is complete the MAX bleeps, LED 2 on the MAX switches on and the
keypad display returns to
2 = MAX Address
.
3.
(MAX software versions 1.23 and 1.32)
Disconnect the
AB line
from the MAX reader. Ensure
that all other modules (keypads, RIOs and on-line MAX readers) are still daisy-chained into the
Galaxy panel. If the MAX reader is the last module on the
AB line
, remove the 680
Ω
end of line
resistor and put it into the last module on the line.
NOTE:
The Galaxy cannot operate if the
AB line
is connected to stand-alone MAX readers with
software V1.23 or V1.32.
4.
The MAX reader is now programmed as a stand-alone module in sleep mode (LEDs 2 – 5 on) and
can be programmed using the MAX cards (refer to Programming Stand-Alone MAX Readers).
Configuring a MAX Reader
Summary of Contents for 3-144
Page 1: ...Galaxy 3 48C 3 144 3 144C 3 520 3 520C Installation Manual Honeywell Security ...
Page 2: ......
Page 8: ...1 2 Galaxy 3 Series Installation Manual ...
Page 10: ...1 4 Galaxy 3 Series Installation Manual ...
Page 50: ...Galaxy 3 Series Installation Manual 3 22 ...
Page 66: ...Galaxy 3 Series Installation Manual 5 8 ...
Page 74: ...Galaxy 3 Series Installation Manual A 8 ...
Page 76: ...Galaxy 3 Series Installation Manual B 2 ...
Page 78: ...Galaxy 3 Series Installation Manual C 2 ...
Page 84: ...E 4 Galaxy 3 Series Installation Manual ...
Page 86: ...Galaxy 3 Series Installation Manual F 2 ...
Page 88: ...1 2 Galaxy 3 Series Installation Manual ...