Chapter 8 High-speed Link
7
Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User
’s Guide R220
Honeywell
January 2019
Items
Description
Communication
module settings
Module
type
Select Pnet I/f module
Base No.
Setting of base position installed
Range of Setting: 0 ~ 7 (varying depending on the CPU module)
Slot No.
Setting of slot position installed
Range of Setting: 0 ~ 11
High-
speed link
index
Setting of High-speed link index number
Range of Setting: 1~12
Communication
period settings
Period
type
- Range of setting: 20ms, 50ms, 100ms, 200ms, 500ms, 1s, 5s, 10s
(default is 20ms)
- This applied to Send data
- But Receive data will be processed in every scan end regardless of
communication period.
Output data
setup in
case of
emergency
settings
CPU
error
Latch
Keeps its output status
(But, P device data is cleared)
Clear
Clears all outputs
CPU
stop
Latch
Keeps its output status
(But, P device data is cleared)
Clear
Clears all outputs
[Table 8.4.2] Setting of communication module
7) Config. Upload
After “Setting of communication module and communication period” is complete, while putting the
mouse cursor on High-speed link window (right screen of SoftMaster
), and select “Online”
“Communication module setting”
“Config. Upload (Dnet, Pnet)” to upload a configuration file.