Chapter 8 High-speed Link
10
Pnet I/F Module 2MLL-PSRA, 2MLL-PMEA, 2MLL-PMEB User
’s Guide R220
Honeywell
January 2019
8.5 High-speed Link Information
With High-speed link service used to exchange data between communication modules of two or more
stations, it provides a checking method of High-speed link service status for the user through High-speed
link information so to confirm reliability of the data read from the destination station via the High-speed link.
In other words, the communication module synthesizes the data received up to that time at intervals of a
specific time and lets the user know if High-speed link operates as in parameters specified by the user
through High-speed link information where the whole information of Run-link(_HSxRLINK) and Link-
trouble(_HSxLTRBL) to provide the whole information of the communication network, and the individual
information of _HSxSTATE, _HSxTRX, _HSxMOD and _HSxERR to provide communication status for
128 register items in the parameters are contained.
The user can use the information in keyword format when programming, and also monitor the High-speed
link status using the monitor function of the High-speed link information. Prior to its application, the user is
requested to check the reliability of the Send/Receive data through High-speed link information of Run-link
and Link-trouble when operating several PLCs with High-speed link used.
[Table 8.5.1] below shows functions and definition of the High-speed link information.
Classification
Run-link
Link-trouble
Send/Receive
status
Operation
Mode
Error
High-speed
link status
Information type
Whole
information
Whole
information
Individual
information
Individual
information
Individual
information
Individual
information
Keyword name
(x=High-speed link No.
n= High-speed link
station No.)
_HSxRLINK _HSxLTRBL
_HSxTRX[n]
(n=0.127)
_HSxMOD[n]
(n=0.127)
_HSxERR[n]
(n=0.127)
_HSxSTATE[n
](n=0.127)
Data type
Bit
Bit
Bit-Array
Bit-Array
Bit-Array
Bit-Array
Monitor
Available
Available
Available
Available
Available
Available
Program
Available
Available
Available
Available
Available
Available
[Table 8.5.1] High-speed link information function
[Figure 8.5.1] Monitor window of variables