background image

VC6800, VC6900 SERIES FLOATING CONTROL VALVES

95C-10828—02

4

INSTALLATION

When Installing This Product...

1.

Read these instructions carefully. Failure to follow 
them could damage the product or cause a 
hazardous condition.

2.

Check the ratings given in the instructions and on 
the product to make sure the product is suitable for 
your application.

3.

Installer must be a trained, experienced service 
technician.

4.

Always conduct a thorough checkout when 
installation is completed.

5.

While not necessary to remove the actuator from the 
body, it can be removed for ease of installation. The 
actuator can be installed in any of the four 
orientations to suit the most convenient wiring 
direction. Actuator latching mechanism works only 
when the lengths of the actuator and the valve body 
are parallel to each other.

6.

An extra 1” (25 mm) head clearance is required to 
remove the actuator.

CAUTION

Disconnect power supply before connecting 
wiring to prevent electrical shock and equipment 
damage.
Never jumper the valve coil terminals, even 
temporarily. This may damage the thermostat.

PLUMBING

The valve may be plumbed in any angle, including vertical 
piping, but preferably not with the actuator below the 
horizontal level of valve body. Make sure there is enough 
room around the actuator for servicing or replacement.

For use in diverting applications, the valve is installed with 
the flow water entering through bottom port AB, and 
diverting through end ports A or B. In mixing applications 
the valve is installed with inlet to A or B and outlet through 
AB.

Mount the valve directly in the tube or pipe. Do not grip the 
actuator while making and tightening up plumbing 
connections. Either hold valve body in your hand or attach 
adjustable spanner (38 mm or 1-1/2") across the 
hexagonal or flat faces on the valve body. (Fig. 4).

Fig. 4. Plumbing of the VC valve.

COMPRESSION MODELS

For compression fitted models, tighten the compression 
nuts enough to make a watertight seal. 
TAKE CARE NOT TO OVER TIGHTEN. 
Maximum torque limit is 45 Nm (33 ft-lb) for the 22 mm 
compression fitting, and 65 Nm (48 ft-lb) for the 28 mm 
compression fitting.

SWEAT MODELS

On sweat fitted valves, the cartridge is shipped loose to 
avoid being damaged during the solder operation.

1.

Remove valve actuator from body and solder the 
connecting pipes in accordance with normal 
soldering practices.

2.

After soldering and valve has cooled, remove 
cartridge assembly from plastic bag, insert into the 
valve body and tighten down with enclosed wrench 
(part# 40007029-002) until it bottoms out. 
DO NOT OVER TIGHTEN (maximum torque is 
4.5 Nm [40 in-lb]). The top surface of the cartridge 
will be flush with the top edge of the body casting.

3.

Replace valve actuator.

M29716

Summary of Contents for VC6800 Series

Page 1: ...changeable and suitable for all valves 1 2 through 1 providing maximum installation flexibility with minimum stocking requirements A locking tab secures the actuator to the body of the valve Multi dir...

Page 2: ...atic 20 Bar 300 psi Burst 100 Bar 1500 psi Valve Material Body of bronze Cartridge of Ryton polyphenylene sulphide and Noryl polyphenylene oxide O ring seals of EPDM rubber Stem of stainless steel Ste...

Page 3: ...1 4 3 8 136 5 11 32 1 2 Flare no adapter 98 3 7 8 111 4 3 8 136 5 11 32 1 2 Inverted Flare no adapter 98 3 7 8 111 4 3 8 136 5 11 32 1 2 BSPP int 15 mm compression 98 3 7 8 111 4 3 8 136 5 11 32 1 2 B...

Page 4: ...oom around the actuator for servicing or replacement For use in diverting applications the valve is installed with the flow water entering through bottom port AB and diverting through end ports A or B...

Page 5: ...actuator off the valve body NOTE The actuator can also be installed at right angles to the valve body but in this position the latch mechanism will not engage 5 Install the new actuator by reversing...

Page 6: ...ck to see if the cartridge needs to be replaced 3 If the motor or other internal parts of the actuator is damaged replace the entire actuator assembly NOTE Resideo hydronic valves are designed and tes...

Page 7: ...VC6800 VC6900 SERIES FLOATING CONTROL VALVES 7 95C 10828 02...

Page 8: ...ell Home trademark is used under license from Honeywell International Inc This product is manufactured by Resideo Technologies Inc and its affiliates www resideo com Resideo Technologies Inc 1985 Doug...