VC6800, VC6900 SERIES FLOATING CONTROL VALVES

95C-10828—02

2

SPECIFICATIONS

Table 1. Actuator Model Identifiers.

** Plenum rated cover & cable.

Table 2. Body Fitting Model Identifiers.

* Includes compression nuts and olives.

For example, to order a 120 second stroke timing actua-
tor, with 1 meter cable and no auxiliary switch, on a 3-
way 3/4" BSPP internal thread body, order 
VC6931MH6111. The last two digits, "11", indicate that 
the actuator comes with conformal coated printed circuit 
board.

Voltage: 

Color coded label

24V, 50-60Hz Model 

Blue

Power Consumption:

4 Watts Max. at nominal voltage (during valve position 

change).

Note:

 Use 6 VA for Class 2 transformer and connection 

wire sizing. Maximum duty cycle 15%.

End Switch Rating:

2.2 A inductive from 5 to 110 Vac
1.0 A inductive above 110 to 277 Vac
Min. DC switching capability: 0.005 A @ 24 Vdc

Note:

 Use model V6831 only for mixed line and low 

voltage applications.

Nominal Timing:

See Table 1 

Note:

 Timing is approximately 20% longer @ 50Hz

Electrical Termination: 3 Versions Available:

1) Molex™ (header #39-30-1060). Requires mating con-

nector (receptacle/housing #39-01-2060), or 

2) With integral 1 meter (nominal 39") leadwire cable

Operating Ambient Temperature:

0 to 65 °C (32 to 150 °F)

Shipping and Storage Temperature:

-40 to +65 °C (-40 to 150 °F)

Atmosphere:

Non-corrosive, non-explosive

Minimum & Maximum fluid temperatures:

1 to 95 °C (34 to 203 °F)

Operating Pressure Differential:

Maximum - 4 bar (60 psi)

Pressure Rating:

Static - 20 Bar (300 psi) 
Burst - 100 Bar (1500 psi)

Valve Material:

Body of bronze
Cartridge of Ryton™ (polyphenylene sulphide) and Noryl™ 

(polyphenylene oxide);

O-ring seals of EPDM rubber;
Stem of stainless steel.

Stem Travel:

10 mm (0.4 inches)

Flow Characteristics:  

Linear

The specifications above are nominal and conform to 
generally acceptable industry standards. Resideo is not 
responsible for damages resulting from misapplication or 
misuse of its products.

Approvals:

Underwriters Laboratories Inc. Listed.
CSA Approved.
CE Approved under EMC 89/336/EEC.

Accessories and Replacement Parts:

40007029-002: Wrench for removing VC cartridge.
VCZZ1100: 2-way characterized cartridge, unit pack.
VCZZ6100: 3-way characterized cartridge, unit pack.

Model 

Series

Voltage

(50/60 Hz)

Auxiliary 

Switch

Nominal 

full open 

time 

@ 60 Hz

Type of 

Electrical 

Connection

VC6830

24 Vac

SPDT

120 sec.

Molex

VC6831

SPDT

1 m cable

VC6930

Molex

VC6931

1 m cable

VC6940

12 sec.

Molex

2-way 

Valve 

Number

Cv 

Rating

Body Fitting

3-way 

Valve 

Number

Cv 

Rating

AA11xx

3.2

1/2” Sweat

MA61xx

3.8

AC11xx

2.1

3/8” Flare

MB61xx

2.7

AD11xx

3.1

1/2” Flare

MC61xx

3.8

AE11xx

3.2

1/2” Inv. Flare

MD61xx

4.2

AF11xx

3.0

1/2” 
BSPP/15 mm int

ME61xx

3.7

AB11xx

3.4

1/2” BSPT int

MN61xx

3.8

AM11xx

4.6

3/4” Sweat

ML61xx

5.9

AH11xx

5.2

3/4” BSPP ext

MG61xx

6.7

AJ11xx

5.2

3/4” BSPP int

MH61xx

6.9

AK11xx

4.7

3/4” BSPT int

MJ61xx

6.2

AL11xx

4.7

3/4” NPT int

MK61xx

6.6

AG11xx

5.4

22 mm 
Compression*

MF61xx

6.9

AP11xx

6.6

1” BSPP int

MP61xx

7.5

AQ11xx

6.2

1” BSPP ext

MQ61xx

7.9

AS11xx

6.2

1” Sweat

MS61xx

6.6

AR11xx

6.6

1” NPT int

MR61xx

8.6

AT11xx

6.6

1” BSPT int

MT61xx

8.1

AN11xx

6.3

28 mm 
Compression*

MM61xx

7.5

Summary of Contents for VC6800 Series

Page 1: ...changeable and suitable for all valves 1 2 through 1 providing maximum installation flexibility with minimum stocking requirements A locking tab secures the actuator to the body of the valve Multi dir...

Page 2: ...atic 20 Bar 300 psi Burst 100 Bar 1500 psi Valve Material Body of bronze Cartridge of Ryton polyphenylene sulphide and Noryl polyphenylene oxide O ring seals of EPDM rubber Stem of stainless steel Ste...

Page 3: ...1 4 3 8 136 5 11 32 1 2 Flare no adapter 98 3 7 8 111 4 3 8 136 5 11 32 1 2 Inverted Flare no adapter 98 3 7 8 111 4 3 8 136 5 11 32 1 2 BSPP int 15 mm compression 98 3 7 8 111 4 3 8 136 5 11 32 1 2 B...

Page 4: ...oom around the actuator for servicing or replacement For use in diverting applications the valve is installed with the flow water entering through bottom port AB and diverting through end ports A or B...

Page 5: ...actuator off the valve body NOTE The actuator can also be installed at right angles to the valve body but in this position the latch mechanism will not engage 5 Install the new actuator by reversing...

Page 6: ...ck to see if the cartridge needs to be replaced 3 If the motor or other internal parts of the actuator is damaged replace the entire actuator assembly NOTE Resideo hydronic valves are designed and tes...

Page 7: ...VC6800 VC6900 SERIES FLOATING CONTROL VALVES 7 95C 10828 02...

Page 8: ...ell Home trademark is used under license from Honeywell International Inc This product is manufactured by Resideo Technologies Inc and its affiliates www resideo com Resideo Technologies Inc 1985 Doug...

Reviews: