background image

VC6800, VC6900 SERIES FLOATING CONTROL VALVES

5

95C-10828—02

TO INSTALL REPLACEMENT ACTUATOR

NOTE:

Installation of a new actuator does not require 
draining the system provided the valve body and 
valve cartridge assembly remain in the pipeline.

1.

Check replacement part number and voltage ratings 
for match with old device.

2.

Disconnect power supply before servicing to avoid 
electrical shock or equipment damage.

3.

Disconnect leadwires to actuator, or depress tab on 
Molex™ connector and remove. Where appropriate, 
label wires for rewiring.

4.

The actuator head is automatically latched to the 
valve. To remove, press up on the latch mechanism 
located directly below the white manual open lever 
with thumb (See Fig. 5). Simultaneously press the 
actuator down towards the body with moderate hand 
force and turn the actuator counter-clockwise by 
1/8 turn (45 degrees).   Lift actuator off the valve 
body.

NOTE:

The actuator can also be installed at right 
angles to the valve body but in this position 
the latch mechanism will not engage.

5.

Install the new actuator by reversing the process in (4).

6.

Reconnect leadwires or Molex™ connector.

7.

Restore power, and check out operation.

Fig. 5. Latch Mechanism to detach Actuator

MANUAL OPENER

The manual opener can be manipulated only when in the 
up position. The “A” port can be opened by firmly pushing 
the white manual lever down to midway and in. In this 
position both the “A” and “B” ports are open, and with 
auxiliary switch models the switch is closed. This "manual 
open" position may be used for filling, venting, or draining 
the system, or for opening the valve in case of power 
failure. The valve can be restored manually to the closed 
position by depressing the white manual lever lightly and 
then pulling the lever out. The valve and actuator will 
return to the automatic position when power is restored.

NOTE:

If the valve is powered open, it can not be 
manually closed unless actuator is removed.

2

Summary of Contents for VC6800 Series

Page 1: ...changeable and suitable for all valves 1 2 through 1 providing maximum installation flexibility with minimum stocking requirements A locking tab secures the actuator to the body of the valve Multi dir...

Page 2: ...atic 20 Bar 300 psi Burst 100 Bar 1500 psi Valve Material Body of bronze Cartridge of Ryton polyphenylene sulphide and Noryl polyphenylene oxide O ring seals of EPDM rubber Stem of stainless steel Ste...

Page 3: ...1 4 3 8 136 5 11 32 1 2 Flare no adapter 98 3 7 8 111 4 3 8 136 5 11 32 1 2 Inverted Flare no adapter 98 3 7 8 111 4 3 8 136 5 11 32 1 2 BSPP int 15 mm compression 98 3 7 8 111 4 3 8 136 5 11 32 1 2 B...

Page 4: ...oom around the actuator for servicing or replacement For use in diverting applications the valve is installed with the flow water entering through bottom port AB and diverting through end ports A or B...

Page 5: ...actuator off the valve body NOTE The actuator can also be installed at right angles to the valve body but in this position the latch mechanism will not engage 5 Install the new actuator by reversing...

Page 6: ...ck to see if the cartridge needs to be replaced 3 If the motor or other internal parts of the actuator is damaged replace the entire actuator assembly NOTE Resideo hydronic valves are designed and tes...

Page 7: ...VC6800 VC6900 SERIES FLOATING CONTROL VALVES 7 95C 10828 02...

Page 8: ...ell Home trademark is used under license from Honeywell International Inc This product is manufactured by Resideo Technologies Inc and its affiliates www resideo com Resideo Technologies Inc 1985 Doug...

Reviews: