HZ322 TrueZONE

®

Zone Panel Professional Installation Guide

HZ332

HEAT 1
HEAT 2
COOL 1
COOL 2

FAN

PURGE

EM HEAT

EMERGENCY HEAT

ZONE 1

ZONE 2

ZONE 3

69-2199-09

Summary of Contents for TrueZONE HZ322

Page 1: ...HZ322 TrueZONE Zone Panel Professional Installation Guide HZ332 HEAT 1 HEAT 2 COOL 1 COOL 2 FAN PURGE EM HEAT EMERGENCY HEAT ZONE 1 ZONE 2 ZONE 3 69 2199 09...

Page 2: ...ondensing Temperature Ratings Shipping 20 F to 150 F 29 C to 66 C Operating 40 F to 165 F 40 C to 74 C Dimensions See Fig 1 Emissions Complies with FCC Class B part 15 requirements Read before install...

Page 3: ...imum Dampers Ambient Temp Maximum Damper VA per Zone 100 F 38 C 28 8 160 F 71 C 16 8 Use an SDCR Slave Damper Control Relay for additional dampers Maximum dampers per panel is limited by trans former...

Page 4: ...e and use the base as a template to drill mounting holes Attach the base to the wall stud roof truss or duct with appropriate screws not included Use two screws for attaching to a stud or roof truss o...

Page 5: ...ne panel To connect wire to the panel strip approximately 1 4 in of insulation and push wire into terminal To release wire press the button on to p of the terminal In retrofit applications trim end of...

Page 6: ...charge Air Temperature Installation Instructions Form Number 69 1521 5 Connect equipment as shown here and on page 5 and 6 6 C7735A1000 M28024 SENSOR DATS DATS 8 Connect a dedicated transform er as sh...

Page 7: ...22 HEAT 1 HEAT 2 COOL 1 COOL 2 FAN PURGE EM HEAT ZONE 1 ZONE 2 ZONE 3 EMERGENCY HEAT M1 M4 M6 R C W1 E W2 Y1 Y2 G O B L Zone 1 DAMPER THERMOSTAT M1 M4 M6 R C W1 E W2 Y1 Y2 G O B L Zone 2 DAMPER THERMO...

Page 8: ...520 72 7 21 25 7 50267 76 7 6 3 5 7 2 1 7 50 1 6 77 2 25 22 1 29 5 25 77 25 7 1 29 5 9 48 30 17 86 6 7 6 0 6285 2 7 25 8 5 1 0 5 1 7 803 5 1 7 50 1 6 25 7 7 0 5 5 66 3725 21 1 9 5 5 7 0 5 25 7 0 5 0...

Page 9: ...CONVENTIONAL NON HEAT PUMP THERMOSTATS OPTIONS TSTAT TIMER ZONES OFF ADVANCED CONFIG NO YES SAVE CHANGES NO YES COMPRESSOR STAGES 1 2 1 2 3 1 AUX HT ENABLED YES NO SET TO YES IF WIRELESS RADIO FREQUEN...

Page 10: ...mit DAT HIGH LIMIT 110 F 180 F 160 F 110 deg F 180 deg F High temperature limit DATS Low Limit DAT LOW LIMIT 30 F 60 F 40 F 30 deg F 60 deg F Low temperature limit OT Temp Enabled OT SENSOR NO YES Dis...

Page 11: ...il the Check out LED lights up Use the Adjust Setting and Next buttons to work through the checkout menu as listed below See the Configuration section on page 7 for instructions on using these buttons...

Page 12: ...be sent to you This warranty does not cover removal or reinstallation costs This warranty shall not apply if it is shown by Resideo that the defect was caused by damage which occurred while the produ...