background image

HZ322 TrueZONE

 

7 69-2199—09

CONFIGURATION

To enter Configuration:

HOME

WIRELESS

MODE

BACK

NEXT

CONFIG

CHECK OUT

ADJUST SETTING

M24799

1

Press the Mode button (the Config LED will 

light up).

HOME

MODE

BACK

NEXT

CONFIG

CHECK OUT

ADJUST SETTING

M24810

WIRELESS

2

Use the Back and Next buttons to navi-

gate through the configuration settings. 

Scroll through the selection choices by 

using the "Adjust Setting" Left and Right 

arrow buttons. Pressing Next enters the 

selected option for that menu item and 

advances to the next menu.

SYSTEM TYPE

[CONV]   HEATPUMP

COOL STAGES

0      [1]     2

CONVENTIONAL

HEATPUMP

HEAT STAGES

0      [1]     2    

RF ENABLED

[YES]      NO

NO

ASKS THIS FOR EVERY WIRED ZONE.

OPTIONS:  HTPUMP-O FOR HEAT PUMP 

THERMOSTATS USING O FOR CHANGEOVER, 

HTPUMP-B FOR HEAT PUMP THERMOSTATS 

USING B FOR CHANGEOVER, AND 

CONVENTIONAL FOR CONVENTIONAL, 

NON-HEAT PUMP THERMOSTATS

OPTIONS: TSTAT, 

TIMER, % ZONES, OFF

ADVANCED CONFIG

[NO]  YES

SAVE CHANGES

[NO]  YES

COMPRESSOR STAGES

[1]     2

1
2

3

1

AUX HT ENABLED

[YES]     NO

SET TO “YES” IF WIRELESS (RADIO FREQUENCY) THERMOSTATS AND THM4000R ADAPTER ARE USED.

2

YES

OPTIONS:  1, 2, 3

ZONES INSTALLED

[3]

OPTIONS:  1, 2, 3

ASKS THIS FOR EVERY ZONE.

ZONES INSTALLED

[3]

RF

“YES” ALLOWS YOU TO VIEW/CHANGE THE ADVANCED 

CONFIGURATION OPTIONS SHOWN ON PAGE 8.

3

4

SHOWN IF COMPRESSR STAGES OR HEAT STAGES IS SET TO 2, OR AUX HT ENABLED IS SET TO “YES”

4 RF MEANS "WIRELESS THERMOSTAT"

STAGE 2 CONTROL

[OFF]

PANEL WILL NOT ASK IF YOU HAVE AUX HEAT WHEN 2 COMPRESSOR STAGES ARE SELECTED. THE HZ432 IS REQUIRED FOR A 3H/2C HEAT-PUMP.

2

1

ZONE 1 TSTAT TYPE

[RF]   WIRED

ZONE 1 TSTAT TYPE

[HTPUMP-O]

WIRED

M28027A

The flow chart below illustrates basic zone panel configuration. For additional configuration, see 

Advanced Configuration on page 8. The label on the inside cover of the HZ322 Zone Panel also con-

tains configuration information.

3

Fig. 13

Fig. 14

Summary of Contents for TrueZONE HZ322

Page 1: ...HZ322 TrueZONE Zone Panel Professional Installation Guide HZ332 HEAT 1 HEAT 2 COOL 1 COOL 2 FAN PURGE EM HEAT EMERGENCY HEAT ZONE 1 ZONE 2 ZONE 3 69 2199 09...

Page 2: ...ondensing Temperature Ratings Shipping 20 F to 150 F 29 C to 66 C Operating 40 F to 165 F 40 C to 74 C Dimensions See Fig 1 Emissions Complies with FCC Class B part 15 requirements Read before install...

Page 3: ...imum Dampers Ambient Temp Maximum Damper VA per Zone 100 F 38 C 28 8 160 F 71 C 16 8 Use an SDCR Slave Damper Control Relay for additional dampers Maximum dampers per panel is limited by trans former...

Page 4: ...e and use the base as a template to drill mounting holes Attach the base to the wall stud roof truss or duct with appropriate screws not included Use two screws for attaching to a stud or roof truss o...

Page 5: ...ne panel To connect wire to the panel strip approximately 1 4 in of insulation and push wire into terminal To release wire press the button on to p of the terminal In retrofit applications trim end of...

Page 6: ...charge Air Temperature Installation Instructions Form Number 69 1521 5 Connect equipment as shown here and on page 5 and 6 6 C7735A1000 M28024 SENSOR DATS DATS 8 Connect a dedicated transform er as sh...

Page 7: ...22 HEAT 1 HEAT 2 COOL 1 COOL 2 FAN PURGE EM HEAT ZONE 1 ZONE 2 ZONE 3 EMERGENCY HEAT M1 M4 M6 R C W1 E W2 Y1 Y2 G O B L Zone 1 DAMPER THERMOSTAT M1 M4 M6 R C W1 E W2 Y1 Y2 G O B L Zone 2 DAMPER THERMO...

Page 8: ...520 72 7 21 25 7 50267 76 7 6 3 5 7 2 1 7 50 1 6 77 2 25 22 1 29 5 25 77 25 7 1 29 5 9 48 30 17 86 6 7 6 0 6285 2 7 25 8 5 1 0 5 1 7 803 5 1 7 50 1 6 25 7 7 0 5 5 66 3725 21 1 9 5 5 7 0 5 25 7 0 5 0...

Page 9: ...CONVENTIONAL NON HEAT PUMP THERMOSTATS OPTIONS TSTAT TIMER ZONES OFF ADVANCED CONFIG NO YES SAVE CHANGES NO YES COMPRESSOR STAGES 1 2 1 2 3 1 AUX HT ENABLED YES NO SET TO YES IF WIRELESS RADIO FREQUEN...

Page 10: ...mit DAT HIGH LIMIT 110 F 180 F 160 F 110 deg F 180 deg F High temperature limit DATS Low Limit DAT LOW LIMIT 30 F 60 F 40 F 30 deg F 60 deg F Low temperature limit OT Temp Enabled OT SENSOR NO YES Dis...

Page 11: ...il the Check out LED lights up Use the Adjust Setting and Next buttons to work through the checkout menu as listed below See the Configuration section on page 7 for instructions on using these buttons...

Page 12: ...be sent to you This warranty does not cover removal or reinstallation costs This warranty shall not apply if it is shown by Resideo that the defect was caused by damage which occurred while the produ...

Reviews: