31
OPERATION
GFCI System
①
120V-30A, 120V/240V-20A (EB4000X),
120V/240V-30A (EB5000X, EB6500X) Receptacles
1. Unplug all tools and appliances from the generator.
2. Start the engine (see page 26).
3. Turn the AC circuit breaker to the ON position.
4. Turn OFF the Auto Throttle switch (see page 27).
5. Press the GFCI TEST button:
• The RESET button should extend, and the AC circuit breaker
should switch to the OFF position.
• If the GFCI and AC circuit breaker do not function as described, take
the generator to an authorized Honda generator dealer for repair.
GFCI TEST BUTTON
GFCI RESET BUTTON
GFCI SYSTEM
①
120V-30A, 120V/240V-20A (EB4000X),
120V/240V-30A (EB5000X, EB6500X) RECEPTACLES
(
)
ON
EB4000X:
120/240 V 20 A RECEPTACLE
EB5000X, EB6500X:
120/240 V 30 A RECEPTACLE
120 V 30 A RECEPTACLE
AUTO THROTTLE SWITCH
AC CIRCUIT BREAKER
GFCI RESET BUTTON
AC CIRCUIT BREAKER
OFF
GFCI TEST BUTTON
(
)