32
OPERATION
6. Press the GFCI RESET button:
• The RESET button should stay in, flush with its base plate.
• With the RESET button in and the engine running, turn the AC
circuit breaker to the ON position. The AC circuit breaker should
remain in the ON position. The AC circuit breaker will not remain
in the ON position if the RESET button is extended.
• If the GFCI and AC circuit breaker do not function as described,
take the generator to an authorized Honda generator dealer for
repair.
• During generator use, if the GFCI RESET button extends and the
AC circuit breaker trips, this usually indicates a faulty power tool,
appliance, or cord.
• If that occurs, perform operation check steps 1 through 6 to verify
that the GFCI and AC circuit breaker are in proper working order. If
the GFCI and AC circuit breaker do test correctly, then the fault is
likely to be in the power tool, appliance, or cord. Repair or replace
the faulty power tool, appliance, or cord before further use.
GFCI RESET BUTTON
AC CIRCUIT BREAKER
ON