LED signals and error messages
LED signals and error messages
54
55
proceed as follows:
•
Press and hold down the operating button until the device LED starts
flashing orange.
•
Press and hold the operating button once again. The device LED
now signalises the current repeater status (red = repeater function off,
green = repeater function on)
•
To change the repeater status, press the operating button again shortly.
•
If there is no operation for 30 seconds, the device will change back
into observation mode and the currently set repeater status is applied.
7.6 Restore factory settings
To remove a wireless smoke alarm from a wireless network, it must
be reset to the initial state. Afterwards, the device can be included into
another wireless network.
To restore the factory settings of the wireless smoke alarm, please
proceed as follows:
•
Press and hold the operating button. After approximately 2 seconds
the device LED starts to flash orange. Still press and hold down the
operating button until the device LED starts flashing red.
•
After releasing the button, the factory settings of the wireless smoke
alarm are restored and the device will be restarted.
8
LED signals and error messages
The current mode of the wireless smoke alarm is indicated optically and
audibly by the following signals:
Operating mode
Operating status
LED display
Audible alarm
Observation mode
red flashing every 43 s
-
Local smoke alarm
red flashing and emergen
-
cy light with subsequent
LED follow-up time of 24
h (fast single flashing for
30 min, afterwards double
flashing every 43 s. Fast
flashing can be aborted by
button press).
intermittent alarm
signal
Alarm transmitted by
other wireless smoke
alarm of the wireless
network
emergency lighting
intermittent alarm
signal
Functional test
Operating status
LED display
Audible alarm
Function test OK
fast red flashing and
emergency lighting while
function test is active with
subsequent muting for
10 min
3 x short alarm sound
Alarm muted
(for 10 minutes)
red flashing every
10 seconds for 10 min
Function test not OK
-
-
Communication test OK
all wireless smoke alarms
flashing green for 5 min
-
Communication test
not OK
-
-
Error messages
Operating status
LED display
Audible alarm
Weak battery
1 x red flashing every 43 s
short beep every 43 s
Weak battery at dif-
ferent wireless smoke
alarm (the alarm of
devices that are receiv-
ing signals cannot be
deactivated)
1 x red flashing every 3 h