background image

critical and will determine the maximum pressure 
experienced by the first enclosure in the series. Advice on 
sizing can be obtained from Hoffman. The test pressure for 
all the enclosures should be 3 times the pressure inside the 
first enclosure when purging is taking place. If PE’s are to be 
connected in parallel each enclosure must have its own 
outlet Relief Valve, Purge Flow Sensor and Pressure Sensor.  
 
1.2 Quality and Installation of the Pressurizing Air or 
Inert Gas Supply 
 
1.2.1 The source of the compressed air must be in a non-
classified area. Inert gas may be used as an alternative to 
compressed air. 
 
1.2.2 Unless a supply shut-off valve has been specially fitted 
within the unit, a valve with the same, or larger, thread size 
as the Control Unit inlet fitting shall be fitted externally. In 
addition, for "Y/Z" Pressurization units, a suitable indicator 
shall be provided. 
 
1.2.3 The tubing and fittings used must conform to 1.1.3 
above. 
 
1.3 Provision and Installation of Alarm Devices 
Hoffman Purge/Pressurization Units have a Minimum 
Pressure Sensor set to a pressure of at least 0.1” WC (0.25 
mbar). When the PE pressure is above this set point the 
Sensor produces a positive "Pressurized" signal. This is 
displayed on a Red/Green indicator. This signal is used to 
operate an electrical contact for a remote “Alarm”, suitable 
for an Intrinsically Safe circuits, in accordance with Hoffman 
drawing 89107938

 

(or for a Non-Incendive circuit in Division 

2)  
 
When the enclosure pressure falls below the set point of the 
Sensor the "Pressurized" signal is removed, i.e. the absence 
of the signal indicates an “Alarm” ("Pressure Failure") 
condition. The user must make use of this external alarm 
facility in accordance with NFPA 496 requirements, if the unit 
“Alarm” indicator is not located in a place where it can be 
readily observed.  
 
The Alarm switch will reset and its contacts can be used to 
operate a remote electrical alarm.  
 
Hoffman application tip: Exception: For a “Z Purge” Unit 
fitted in a Division 2 area, a non-classified switch inside 
the PE can be used to operate a remote Alarm provided 
its electrical supply comes from within the PE (i.e. NOT 

PROVIDING DRY CONTACTS). When the PE power is 
switched off there is no need for an alarm. 
 
1.4 Power Supplies and their Isolation 
 
1.4.1
 All power entering the PE shall be provided with a 
means of isolation. This requirement also applies to any 
external power sources that are connected to "dry contacts" 
or "volt-free contacts" within the PE. Exception: Power to 
Intrinsically Safe, or other apparatus, which is already 
suitable for the location, need not be isolated by the Hoffman 
Purge/Pressurization unit. When utilizing "Y/Z" 
Pressurization the power may be controlled manually by the 
user by the use of local isolating switch.   
 
1.4.3 The Power (cut-off) Switch must be approved for the 
location or located in a non-classified area.  
 
1.4.4 No valves are permitted between the Power Switch 
and the Hoffman Purge/Pressurization Unit. 
 
 
1.5 Marking  
 
1.5.1
 The Hoffman Purge/Pressurization Unit

 

carries a 

nameplate and a specification sheet, which give specific 
data such as serial and models numbers, Pressure Sensor 
settings, flow rates and purge time.  
 
1.5.2 Other marking, for the PE, required by the standard 
includes:  
 

WARNING - PRESSURIZED ENCLOSURE 
This enclosure shall not be opened unless the 
area is known to be free of flammable materials 
or unless all devices within have been de-
energized" "Power shall not be restored after the 
enclosure has been opened until the enclosure 
has been purged for ____ minutes at a flow rate 
of _____."  

 
Note: It is understood that NFPA 496 requires de-energizing 
of all devices that are not suitable for the hazard, e.g. 
devices that are not Explosionproof or Intrinsically Safe. For 
example, an explosionproof anti-condensation heater would 
not have to be de-energized.  
 
1.5.2 If Inert Gas is used as the Protective Gas and a risk of 
asphyxiation exists, a suitable warning plate should be fitted 
to the PE.  

 

Section 2 Operation of the Unit

 

 
Initial Commissioning  
 
2.1
 Check that the unit has been installed in accordance with 
Section 1 of this manual.  
 
2.2 Disconnect the supply pipe from the inlet to the Control 
Unit and blow clean air through for at least 5 seconds per 
foot of length (15 sec / meter) to remove any debris, oil and 
condensation.  
 
2.3  Connect a temporary pressure gauge or liquid 
 manometer to the PE or Control Unit “Pressure Test Point”, 
[on the LP Sensor, by the removal of the Red plug - 5/32” 
(4mm) OD nylon tube].  

 

2.4  Open the supply shutoff valve. 

 

2.5  Adjust the Flow Control Valve (FCV) so that the 
enclosure pressure rises to the point where the 
“Pressurized” indicator turns Green. 

 

2.6  Continue to raise the PE pressure until the Relief Valve 
(RLV) opens.  Verify that the RLV opens at or below the 
figure specified in the documentation.  Repeat the test 
several times. 

 

2.7  Lower the PE pressure until the “Pressurized” indicator 
turns Red.  Verify that the indicator turns Red at or above the 
pressure specified in the documentation. Check the external 
alarm contacts. 
 
Note: On Hoffman CF units the Minimum Pressure Sensor 
set point may be significantly above the minimum of 0.1wc 

Summary of Contents for PCFB1YZ

Page 1: ...ication Sheet CF Y Z Purge Pressurization Unit 2 Application Suitability 3 Installation Operation and Maintenance for CF Units Section 0 Description and Principle of Operation Section 1 Installation o...

Page 2: ...anada NFPA 496 UL E466718 Class I Div 1 Class I Div 2 Groups A B C D Groups A B C D For limitations and conditions of use refer to the applicable certificate at the back of this manual Supply Pressure...

Page 3: ...t be fitted to the Pressurized Enclosure The following materials are used in the construction of Hoffman Purge Pressurization Units If substances that will adversely affect any of these materials are...

Page 4: ...alibrated Outlet Orifices Where the Outlet Orifice disk is removable and can be easily changed by the user to give different flow rates according to the size of the PE and the available air supply cap...

Page 5: ...the PE Exception Power to Intrinsically Safe or other apparatus which is already suitable for the location need not be isolated by the Hoffman Purge Pressurization unit When utilizing Y Z Pressurizat...

Page 6: ...the RLV and any other Spark Arrestors Remove any debris or corrosion or replace the Spark Arrestor with a spare Check the condition of the air supply filter element Clean or replace it as necessary 3...

Page 7: ...le cause 2 Excessive Pressurized Enclosure PE leakage Check around the PE when flow is taking place Any significant leakage must be cured Has a Leakage Test been done The total leakage should not exce...

Page 8: ...Arrestor with circle clip Fix Spark Arrestor to Enclosure ensuring that Control Unit and Spark Arrestor are diagonally opposed 5 Connect output dry contact alarm as required 6 Connect isolated air su...

Page 9: ...Quick Installation Guide PCFF1YZ...

Page 10: ...clip Fix Spark Arrestor to Enclosure ensuring that Control Unit and Spark Arrestor are diagonally opposed 5 Connect output dry contact alarm as required 6 Connect isolated air supply to Control Unit 7...

Page 11: ...Spark Arrestor Orifice Relief Valve Drawing...

Page 12: ...Relief Valve Position Relief Valve Cutout Schematic for both PCFB1YZ and PCFF1YZ...

Page 13: ...instructions and Article 504 of the NEC ANSI NFPA 70 3 For guidance on Installation see ANSI ISA RP12 6 Installation of IS Instrument Systems in Class I Hazardous Locations 4 Voc or Vt of associated a...

Page 14: ......

Page 15: ......

Page 16: ...Hoffman Enclosures Inc 2100 Hoffman Way Anoka Minnesota 55303 1745 USA Phone 763 422 2211 www hoffmanonline com P N 89108870 Dwg 89109562 A...

Page 17: ......

Reviews: