- Has the PE door been closed and all conduit/cable glands 
sealed? 
 
- Is the PE leaking too much?  
 
Possible cause 3: Air supply fault? 
 
Insufficient purge Flow due to inadequate air supply 
pressure/flow. Check the air supply pressure at the inlet to 
the CU 
when flow is taking place. Excessive pressure drop 
in the supply pipe is very common cause of this problem. 
The supply pipe must be at least as big as the CU inlet fitting. 
i.e. at least ½” NB. 
 
Possible cause 4: Excessive PE Leakage? 
 
Check around the PE when flow is taking place.  Any 
significant leakage must be cured. Has a Leakage Test been 
completed?  The total leakage should not exceed 10% of the 
Continues Flow rate. 
Possible cause 5: PE not strong enough? 
 
Repeat the PE Pressure Test.  FM recommend that the PE 
is tested to three times the Relief Valve opening pressure 
e.g. 12”wc (30 mbarg) for standard units.  Has this test been 
done?   
 
Possible cause 6: Unit fault?  
 
Has the pressure sensor tube been damaged? 
If checks above reveal that the PE is correct, the fault 
probably lies in the Control Unit. The basic operation of the 
Minimum Pressure Sensor can be checked by unscrewing 
the 2.4” (60mm) diameter diaphragm and, by using a finger, 
block the threaded hole in the top of the valve module. The 
valve should operate and the indicator should turn Green. If 
this works correctly and the enclosure pressure is above the 
setting of the Minimum Pressure Sensor it is likely that the 
Pressure Sensor diaphragm needs re-calibrating or 
replacing. (See 4.6)  
 
4.3 Relief Valve Opens (Continuously or Intermittently)  
 
Possible cause 1:
 The PE pressure is too high. The Flow 
Control Valve (FCV) is too far open. Adjust the FCV as 
described in Section 2 above.  
 
Possible cause 2: Debris on the RLV disk allowing air to 
leak from the valve. Remove the RLV cover and clean the 
valve disk. The disk and spring may be removed from the 
RLV without affecting the calibration.  
 
4.4 “Purging” Indicator Will Not Turn Green During 
Purging
  
 
Possible cause 1: Insufficient purging Flow due to 
inadequate air supply pressure. Check the air supply 
pressure at the inlet to the CU when flow is taking place. 
Excessive pressure drop in the supply pipe is a very 
common cause of this problem. The supply pipe must be at 
least as big as the CU inlet fitting, i.e. at least ½” NB (12 
mm).  

 
Possible cause 2: Excessive Pressurized Enclosure (PE) 
leakage. Check around the PE when flow is taking place. 
Any significant leakage must be cured. Has a Leakage Test 
been done? The total leakage should not exceed 10% of the 
Purge Flow Sensor setting. Check for leakage down the 
conduit through unsealed stopping boxes.  
 
Possible cause 3: PE not strong enough. Repeat the PE 
pressure test. It is recommended that the PE is tested to 
three times the Relief Valve opening pressure e.g. 12”WC 
(30 mbar) for units with default settings.  
 
Possible cause 4: The tubing from the RLV Flow Sensing 
point to the Purge Flow Sensor is not air-tight e.g. fitting nuts 
not tightened or tube damaged. Check and repair as 
necessary.  
 
Possible cause 5: The Purge Flow Sensor is not operating 
correctly or out of calibration. The basic operation of the 
Purge Flow Sensor can be checked by unscrewing the 2.4” 
(60 mm) diameter diaphragm and by using a finger, block 
the threaded hole in the top of the valve module. The valve 
should operate and the indicator turn Yellow. If this works 
correctly and the flow through the Relief Valve is above the 
minimum required WITH THE RELIEF VALVE COVER 
FIRMLY SECURED IN PLACE the Sensor diaphragm needs 
re-calibrating or replacing.  
 
4.5 Pressure Sensor Calibration  
 
If it is decided that the Minimum Pressure Sensor 

/

 Purge 

Flow Sensor needs re-calibrating it can either be returned to 
Hoffman for this service or it can be done by the user as 
follows:  
 
Disconnect the pressure sensing pipe from the top of the 
diaphragm. (It is a “push-in” quick release fitting; firmly push 
inwards the collar surrounding the pipe where it enters the 
fitting, and then pull the pipe outwards while maintaining the 
pressure on the collar). Unscrew the 2.4” (60 mm) diameter 
diaphragm housing from the top of the Sensor. Invert it and 
note the brass adjusting screw in the center. Turning the 
screw inwards (clockwise) will lower the setting. It is likely 
that the screw will be very stiff due to the locking sealant. If 
the screw cannot be moved the application of gentle heat in 
the area of the brass screw can often help. DO NOT 
OVERHEAT!  
 
4.6 Filter Cleaning  
 
If the filter element needs cleaning the transparent bowl can 
be unscrewed and removed. The filter element also 
unscrews and can then be cleaned in soapy water. Do not 
use solvents on any part of the filter assembly.  
 
It is sometime easier, if the bowl is very tight; to remove the 
filter by undoing the fitting that holds the filter into the Control 
Unit.  
 

 
 
 
 
 
 

Summary of Contents for PCFB1YZ

Page 1: ...ication Sheet CF Y Z Purge Pressurization Unit 2 Application Suitability 3 Installation Operation and Maintenance for CF Units Section 0 Description and Principle of Operation Section 1 Installation o...

Page 2: ...anada NFPA 496 UL E466718 Class I Div 1 Class I Div 2 Groups A B C D Groups A B C D For limitations and conditions of use refer to the applicable certificate at the back of this manual Supply Pressure...

Page 3: ...t be fitted to the Pressurized Enclosure The following materials are used in the construction of Hoffman Purge Pressurization Units If substances that will adversely affect any of these materials are...

Page 4: ...alibrated Outlet Orifices Where the Outlet Orifice disk is removable and can be easily changed by the user to give different flow rates according to the size of the PE and the available air supply cap...

Page 5: ...the PE Exception Power to Intrinsically Safe or other apparatus which is already suitable for the location need not be isolated by the Hoffman Purge Pressurization unit When utilizing Y Z Pressurizat...

Page 6: ...the RLV and any other Spark Arrestors Remove any debris or corrosion or replace the Spark Arrestor with a spare Check the condition of the air supply filter element Clean or replace it as necessary 3...

Page 7: ...le cause 2 Excessive Pressurized Enclosure PE leakage Check around the PE when flow is taking place Any significant leakage must be cured Has a Leakage Test been done The total leakage should not exce...

Page 8: ...Arrestor with circle clip Fix Spark Arrestor to Enclosure ensuring that Control Unit and Spark Arrestor are diagonally opposed 5 Connect output dry contact alarm as required 6 Connect isolated air su...

Page 9: ...Quick Installation Guide PCFF1YZ...

Page 10: ...clip Fix Spark Arrestor to Enclosure ensuring that Control Unit and Spark Arrestor are diagonally opposed 5 Connect output dry contact alarm as required 6 Connect isolated air supply to Control Unit 7...

Page 11: ...Spark Arrestor Orifice Relief Valve Drawing...

Page 12: ...Relief Valve Position Relief Valve Cutout Schematic for both PCFB1YZ and PCFF1YZ...

Page 13: ...instructions and Article 504 of the NEC ANSI NFPA 70 3 For guidance on Installation see ANSI ISA RP12 6 Installation of IS Instrument Systems in Class I Hazardous Locations 4 Voc or Vt of associated a...

Page 14: ......

Page 15: ......

Page 16: ...Hoffman Enclosures Inc 2100 Hoffman Way Anoka Minnesota 55303 1745 USA Phone 763 422 2211 www hoffmanonline com P N 89108870 Dwg 89109562 A...

Page 17: ......

Reviews: