background image

1. 

With aid of supplied mounting template, cut mounting holes into enclosure.  Ensure that Control Unit and Relief Valve are 
diagonally opposed. 
 

2. 

Fix Control Unit to enclosure 

 

3. 

Fix Relief Valve to enclosure 

 

4. 

For Continuous Flow units only, select orifice for required purge flow rate and fit into Spark Arrestor with circle-clip.  Fix 
Spark Arrestor to Enclosure ensuring that Control Unit and Spark Arrestor are diagonally opposed. 
 

5. 

Connect output (dry contact alarm) as required 
 

6. 

Connect isolated air supply to Control Unit 
 

7. 

Ensure enclosure door is closed, fully latched and free of leaks 
 

8. 

Turn on 60 PSIG (4 bar) air supply (115 PSIG/8 bar max)  
 

9. 

Slowly increase Flow Control Valve until Alarm Indicator turns from RED to GREEN 
 

10.  After Purge time has been completed power can  be applied to the enclosure 

 

11.  Refer to manual for assistance 

 

 

 
 
 
 
 
 
 
PCFF1YZ 
 

Summary of Contents for PCFB1YZ

Page 1: ...ication Sheet CF Y Z Purge Pressurization Unit 2 Application Suitability 3 Installation Operation and Maintenance for CF Units Section 0 Description and Principle of Operation Section 1 Installation o...

Page 2: ...anada NFPA 496 UL E466718 Class I Div 1 Class I Div 2 Groups A B C D Groups A B C D For limitations and conditions of use refer to the applicable certificate at the back of this manual Supply Pressure...

Page 3: ...t be fitted to the Pressurized Enclosure The following materials are used in the construction of Hoffman Purge Pressurization Units If substances that will adversely affect any of these materials are...

Page 4: ...alibrated Outlet Orifices Where the Outlet Orifice disk is removable and can be easily changed by the user to give different flow rates according to the size of the PE and the available air supply cap...

Page 5: ...the PE Exception Power to Intrinsically Safe or other apparatus which is already suitable for the location need not be isolated by the Hoffman Purge Pressurization unit When utilizing Y Z Pressurizat...

Page 6: ...the RLV and any other Spark Arrestors Remove any debris or corrosion or replace the Spark Arrestor with a spare Check the condition of the air supply filter element Clean or replace it as necessary 3...

Page 7: ...le cause 2 Excessive Pressurized Enclosure PE leakage Check around the PE when flow is taking place Any significant leakage must be cured Has a Leakage Test been done The total leakage should not exce...

Page 8: ...Arrestor with circle clip Fix Spark Arrestor to Enclosure ensuring that Control Unit and Spark Arrestor are diagonally opposed 5 Connect output dry contact alarm as required 6 Connect isolated air su...

Page 9: ...Quick Installation Guide PCFF1YZ...

Page 10: ...clip Fix Spark Arrestor to Enclosure ensuring that Control Unit and Spark Arrestor are diagonally opposed 5 Connect output dry contact alarm as required 6 Connect isolated air supply to Control Unit 7...

Page 11: ...Spark Arrestor Orifice Relief Valve Drawing...

Page 12: ...Relief Valve Position Relief Valve Cutout Schematic for both PCFB1YZ and PCFF1YZ...

Page 13: ...instructions and Article 504 of the NEC ANSI NFPA 70 3 For guidance on Installation see ANSI ISA RP12 6 Installation of IS Instrument Systems in Class I Hazardous Locations 4 Voc or Vt of associated a...

Page 14: ......

Page 15: ......

Page 16: ...Hoffman Enclosures Inc 2100 Hoffman Way Anoka Minnesota 55303 1745 USA Phone 763 422 2211 www hoffmanonline com P N 89108870 Dwg 89109562 A...

Page 17: ......

Reviews: