Modbus Communications 42
HP-327
HIT-4U
Fault Codes
The following table defines each bit for the fault codes returned when
polling register 7022 and 7023 using function code 03. When a value of 1
is returned for a bit, it indicates that the fault has occurred since last power
on (7022) or is currently active (7023).
Bit Fault
0
Reset, brownout
1
Reset, reset pin
2
Reset, DoBOR
3
Reset, wakeup from LPM5
4
Reset, security violation
5
Reset, supply voltage supervisor low
6
Reset, supply voltage supervisor high
7
Reset, supply voltage monitor low
8
Reset, supply voltage monitor high
9
Reset, DoPOR
10
Reset, watchdog timer timeout
11
Reset, watchdog timer key violation
12
Reset, flash key violation
13
Reset, PLL unlock
14
Reset, peripheral/configuration area fetch
15
Reset, power management key violation
16
Low battery
17
Pulse output overflow
18
Alarm, rate low
19
Alarm, rate high
20
Alarm, total
21
Flash segment 1 invalid
22
Flash segment 2 invalid
23
Maximum input frequency exceeded
24
EEPROM read error on startup
25
Code execution error
26
Flow rate exceeds 20mA setting
27
Spare 5
28
Spare 4
29
Spare 3
30
Spare 2
31
Spare 1
Flow-Tech, Inc. | In MD 410-666-3200 - In VA 804-752-3450 | www.flowtechonline.com