![Hochiki HCP 1000 Series Installation And Operation Manual Download Page 5](http://html1.mh-extra.com/html/hochiki/hcp-1000-series/hcp-1000-series_installation-and-operation-manual_2143415005.webp)
Page 3 of 52
1.0 INTRODUCTION
Introduction :
Hoc hik i’s
SERIES HC P 1000 Fire Alarm Con trol Units
provide a large capa city o f sup ervised Cla ss A o r B (UL S tyle
D or B) Initiating Circuits, and supervised Class A or B (UL Style Z or Y) Indicating Circuits. All Circuits are supervised
for opens and ground faults, and Indicating Circuits for shorts. Optional Modules include additional Initiating and
Indicating Circuits, Relay, and Polarity Reversal & City Tie. Flush or surface mountable enclosures can be used for
retrofits and on new installations.
1.1 Overall Features:
T
Ba sic unit has 8 Class B (Style B) Initiating Circuits which may be configured as 4 C las s A (Style D) Circuits.
These are configurable as Alarm, Verified Alarm, W aterflow Alarm, Sprinkler Alarm, Latching or Non-Latching
Su pe rvis ory, or Troub le-Only Circuits. There are two LED’s per Circuit; one for Trouble (Amber), and one for
Status (Red /Am ber).
T
Basic unit has 4 Power Limited Class A/B (Style Z/Y) Indicating Circuits with individual trouble indicators. Each
Circuit can be co nfigured as Au dible (silencea ble) or Vis ua l (no n-silenc ea ble). Aud ibles m ay be stea dy,
Tem poral Code, California Code, or March Time.
T
Initiating and Indicating Circuits may be individually Disconnected by a DIP Switch (Slide-Switch on “S”
Versions for the U SA M arket only).
T
Co nfigu rable Sign al Silenc e Inh ibit, Auto Sign al Silenc e, T wo- Stag e O pera tion, O ne-M an W alk T est.
T
Subsequent Alarm, Supervisory, and Trouble operation
T
Tw o ou tputs for 4 w ire res ettab le sm ok e po wer sup ply (200 m A ea ch M ax., 3 00 m A tota l Max.)
T
Auxiliary Relay Contacts for Comm on Alarm and Com mon Supervisory (disconnectable), and a Com mon
Troub le re lay.
T
RS-485 Interface for HRA-1000 Series Rem ote Multiplex Annunciators.
T
Optional Mod ules for additio na l Initia ting , Ind ica ting , & R elay Circu its,& City Tie & Polarity Reversal Signalling.
T
Easy Configuration via Push-Buttons and Switches.
T
Extensive transient protection
T
Su rfa ce Mou nta ble En clo su res, F lus h T rim s A vailable
1.2 Controls and Indicators:
8 Pu sh-Buttons , 16 C om m on In dicators, p rovision fo r up to 24 C ircuits
(Expansion Chassis adds provision for up to another 48 Circuits)
firealarmresources.com